OperationandProgrammingManual
11

MonitorMode(operatingmode=01)
MonitorModeisusedforapplicationswhereitisimportantonlytomonitorflowratesandtotals.This
modealsoprovidesanalogandlimitoutputs.Thepro grammablelimitvaluesturnarelaycontacteither
ONorOFF.The420mAor05voltanalogoutputscanbescaledto
theflowrateorthetotal,whichcan
berecordedinstripchartform,asadigitalrecording,orsenttoaPLCviatheserialcommunicationlink.
Ifonlyflowrateandtotalizationarerequired,entertheprogrammingmode(F4),selectGeneralA(F2)
andprogramthedesiredvariables
(seepage24forspecificdetails).Orforuseofgenericflowrateand
totalizationfactorsandengineeringunits,enter theQuickProgrammin gselection (s eepage32).
Ifanalogoutputsorlimitsaretobeusedinthemonitormode,programthefollowingadditional
variables:
ANALOGGAINFACTOR:Scalesthe
mAorthevoltageout.
POINTER:Addressforthevariablethatshouldbeexpressed.
OFFSET:AprogrammedmAmporvoltageoutput,whichcorrespondstoazeroinputfrequency.
LIMITOUTPUTS:Seepage15forfurtherprogramming.
Whenshipped,thechannelcardsare inmonitormode.However,the
4optocouplers,pins11,12,13
and14aresetforthePIDmodeinthatthreeofthemareinputsandoneisanoutput.Apincanbe
eitheraninputoranoutputdependingonthewaytheoptocouplerchipisset.Ifyouselectthe
monitor
modeandwishtousethelimits,thenmovetheoptocouplerchipstomakethepinsfunctional.To
changetheInput/Outputchips,refertotheINPUT/OUTPUTsectiononpage14.
PIDMode02(operatingmode=02)
ThePIDmode02isdesignedtocontrolfluidflows.TohavetheEMO3000operateinPID,itisnecessary
toprepareseveralPIDvariables.
Beforechangingmodesandvariables,disconnectthecontrolvalvesandallcontrolsignals(suchashold,
transparent,etc.).
ImportantVariablestoProgramforPIDOperation
(FordetailsaboutprogrammingtheEMO3000withtheDM3000,seepage23.)
Proportional Thisfactordeterminesthestrength(orstiffness)oftheclosedloop
control.Inmany
cases,onlyexperimentationcandeterminethisfactor.Startwitharelativelylownumber(between10
and20);toolargeanumbercancauseoscillations.
Notice