28

Whenthedesiredvariableismovestothearrow,selectF4=PROGRAM.TheDM3000thenasksforthe
passcode.
ENTERPASSCODE=XXXX
Thecodeis4146.
Keyinthecorrectvariablevalueand EnterwithF6. 
TheLimitRulesaresetupsothatbyentering
oneoffourtwonumbercombinationsforeachofthefour
limits,youcanselectthevariablethatdeterminestheoperatingfunctionaccordingtothetablebelow.
11‐‐‐TotalLimitforAinput
12‐‐‐FlowRateLimitforAinput
13‐‐‐RatioErrorLimitforA
21‐‐‐TotalLimitfor
Binput
22‐‐‐FlowRateLimitforBinput
23‐‐‐RatioErrorLimitforB
2=RATIOS
***RATIOS***CH=003
‐‐‐‐> RATIO1+/% =XXXXX.
RATIO2+/% =XXXXX.
RATIO3+/% =XXXXX.
RATIO4+/% =XXXXX.
F1=ESC F2=PGUP F3=PGDN F4=PRG


TheRatiosscreenallowsyoutosettheerrorpercentageatwhichtheLimitsturnson,iftheEMO3000is
inRatiooperatingmode.ThecalculationfortheactualRatiois:inputA/inputB.TheIdealRatioisstrictly
aprogrammablepointthedesiredratioholds.Therefore,thepercentage
oferrorbetweentheActual
andIdealRatiocancontroltheLimitoutputsifyouprogramitthatway.Forexample,ifyouprogramthe
IdealRatioto2(2to1ratio),andtheActualRatiomeasuredis2.2,thepercentageoferrorbetweenthe
twois10%.Ifthe
LimitRuleissetforRatioandyouprogramtheRatioerrorpercentfor10%orless,the
limitoutputturnsON.