Power LED
4 operating status LED indicate the current status of the voltage supply, module mode and error messages.
LED
Logical status
1
PWR (green)
ON = correct voltage supply to the module electronics
RUN/STOP BUTTON
The Run/Stop control button replaces the former control switch.
This slightly changes the operating concept:
Action
Command
Submarine, boot phase
Activation of the pushbutton
Change into PPP mode or submarine
console
CODESYS PLC/ CP1131-P
Short push
Change between RUN and STOP mode
of PLC
Long push
STOP the PLC using RESET of the vari-
ables, but not the retain data (correspon-
ding to the activation of the rocker switch
on the DC1000 modules)
It is then no longer possible to force-hold the PLC controller in the STOP state!
LEDs: RUN/STOP ERROR - LED signalisation
2 LED are available on the module to signalise the system status (RUN/STOP in two colours:
red/green/(yellow); ERROR in red only). The flash codes familiar from the DC1000 are therefore no longer
applicable. The following system states are signalised via the LED:
System states
LED RUN/STOP
LED ERROR
PPP configuration mode active
Yellow
Off
USB packet update active
Yellow, flashing
Off
System error
Off
On
PLC states
RUN
Green
Off
STOP
Red
Off
Error stop
Red
On
Reset button registered
Red, flashing
Off
Applicatory states
Identification of ProfiNET device
Yellow, flashing
Flash