ORDERING INFORMATION
Catalog # Description
LS-101 Light Sensor controller: Range 1 -1400
footcandles
B series Power packs Output 24 VDC; 150 mA
B120E-P 120 VAC; 60 Hz
B277E-P 277 VAC; 60 Hz
B230E-P 220-240 VAC; 50-60 Hz
B347D-P 347 VAC; 60 Hz
BZ-100 Power pack 120/277 VAC; 60 Hz, Output 24 VDC; 150mA
with
Hold-ON and Hold-OFF inputs
WARRANTY
Watt Sto p p e r / L e g rand warranties its products to be free of
d e fects in materials and workmanship for a period of five
ye a rs . T h e r e are no obligations or liabilities on the part of
Watt Sto p p e r / L e g r and for consequential damages arising out
of or in connection with the use or perfo r m a n c e of this
p roduct or other indirect damages with respect to lo ss of
p ro p e r t y, revenue, or pro fit, or co st of re m o val, installation or
re i n s ta l l a t i o n .
2800 De La Cruz Bouleva rd, Santa Clara, CA 95050
Te c h n i cal Support: 800.879.8585 • www. w a t t s to p p e r. c o m
07076r2 4/2007
LED STATUS INDICATOR
O f f . . . . . . . . . . . . . . . .The lights are commanded ON by the
L S -1 0 1
On solid gre e n . . . . . .The lights are commanded OFF by
the LS-1 0 1 .
Flashing green, once per seco n d
The LS-101 is in Te s t Mode
Flashing green, once every four seco n d s
A u tomatic co n t r ol of the lighting is
being overridden either by the wall
s w i tch or from the LS-101’s Contro l
m e n u .
TROUBLESHOOTING
Display does not display any info r m a t i o n
P r e ss either button to wake up the display.
Verify that the LS-101 is being powe red with 24 VDC.
Lights do not switch when desire d
Use the CTRL menu to manually te st ON and OFF co n t r ol of
the lighting. If the lights switch with manual co n t rol, then
check the ON and OFF setpoints.
Use te st mode to verify setpoints.
Use the fo o tca n d l e display screen to co m p a r e the curre n t
values with the setpoints.
LED is OFF
If the co n t r o l l ed lights are ON, then the LED is like ly
o p e rating co r r e c t ly.
LED is blinking
If the blink is slow (one blink every four seconds) then the
L S - 1 0 1 ’s output has been fo rced ON or OFF by an ove r r i d e ,
f r om the optional wall switch, or the Control menu.
If the blink is fa s t (one blink every second) then the LS-101
is in te st mode.