PERMEATE (PRODUCT WATER) CONNECTION
Locate the 1” connection labeled permeate and attach to storage tank. Ensure that the
permeate water can flow freely with no backpressure. Backpressure can cause
irreversible damage to the membrane elements. The 1” permeate line can be run to the
holding tank with PVC fittings, or other FDA approved materials. This is so the material
being used does not dissolve into the permeate water.
CAUTION THE PH OF THE REVERSE OSMOSIS PERMEATE WATER WILL
TYPICALLY BE 1-2 POINTS LOWER THAN THE FEED WATER PH. A LOW PH CAN
BE VERY AGGRESSIVE TO SOME PLUMBING MATERIALS SUCH AS COPPER
PIPING.
CONCENTRATE (WASTE WATER) CONNECTION
Locate the 1” connection labeled concentrate and attach to a drain. Run the concentrate
line to an open drain in a free and unrestricted manner (no backpressure).
CAUTION: ANY RESTRICTIONS OR BLOCKAGE IN THE DRAIN LINE CAN
CAUSE BACKPRESSURE, WHICH WILL INCREASE THE SYSTEM’S OPERATING
PRESSURE. THIS CAN RESULT IN DAMAGE TO THE SYSTEM’S MEMBRANES AND
COMPONENTS.
ELECTRICAL
The motor used on the CT-Series systems are pump and motor combination. The motor
is available in 220/380/460 Volt, 50/60 Hertz, 1 Phase/3 phase. Each CT-Series system
is equipped with a 5 foot electrical cord.
Ensure that the electrical circuit supplying the system is compatible with the
requirements of the specific CT model you are installing.