User manual

AXISA1001NetworkDoorController&AXISEntryManager
TechnicalSpecifications
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
DoorConnector
Two4-pinterminalblocksfordoormonitoringdevices(digitalinput).
Alldoorinputpinscanbesupervised.Iftheconnectionisinterrupted,analarmistriggered.To
usesupervisedinputs,installendoflineresistors.Usetheconnectiondiagramforsupervised
inputs.Seepage64.
FunctionPinNotes
Specications
0VDC(-)
1,3
0VDC
Input
2,4
Forcommunicatingwithdoormonitor.
DigitalinputConnecttopin1or3respectivelyto
activate,orleaveoating(unconnected)todeactivate.
Note:Thispincanonlybeusedforinput.
0tomax40VDC
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
AuxiliaryConnector
4-pincongurableI/Oterminalblockfor:
Auxiliarypower(DCoutput)
DigitalInput
DigitalOutput
0VDC(-)
Foranexampleconnectiondiagram,seeConnectionDiagramsonpage63.
FunctionPinNotes
Specications
0VDC(-)
1
0VDC
DCoutput
2
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedaspowerout.
3.3VDC
Maxload=100mA
DigitalinputConnecttopin1toactivate,orleave
oating(unconnected)todeactivate.
0tomax40VDC Congurable
(InputorOutput)
3–4
DigitaloutputConnecttopin1toactivate,orleave
oating(unconnected)todeactivate.Ifusedwithan
inductiveload,e.g.arelay,adiodemustbeconnected
inparallelwiththeload,forprotectionagainstvoltage
transients.
0tomax40VDC,opendrain,
100mA
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
61