User manual

AXISA1001NetworkDoorController&AXISEntryManager
TechnicalSpecications
FunctionPinNotes
Specications
0VDC(-)
1,3
0VDC
Input
2,4
Forcommunicatingwithdoormonitor.
DigitalinputConnecttopin1or3respectivelyto
activate,orleaveoating(unconnected)todeactivate.
Note:Thispincanonlybeusedforinput.
0tomax40VDC
AuxiliaryConnector
4-pincongurableI/Oterminalblockfor:
Auxiliarypower(DCoutput)
DigitalInput
DigitalOutput
0VDC(-)
Foranexampleconnectiondiagram,seeConnectionDiagrams,onpage52.
FunctionPinNotes
Specications
0VDC(-)
1
0VDC
DCoutput
2
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedaspowerout.
3.3VDC
Maxload=100mA
DigitalinputConnecttopin1toactivate,orleave
oating(unconnected)todeactivate.
0tomax40VDC Congurable
(InputorOutput)
3–4
DigitaloutputConnecttopin1toactivate,orleave
oating(unconnected)todeactivate.Ifusedwithan
inductiveload,e.g.arelay,adiodemustbeconnected
inparallelwiththeload,forprotectionagainstvoltage
transients.
0tomax40VDC,opendrain,
100mA
PowerConnector
2-pinterminalblockforDCpowerinput.UseaSafetyExtraLowVoltage(SELV)compliant
limitedpowersource(LPS)witheitheraratedoutputpowerlimitedto100Woraratedoutput
currentlimitedto5A.
WhenusedinsystemsthatrequireULcertication,theproductshallbepoweredbyaUL
294-listedorUL603-listedClass2low-voltagepowerlimitedpowersupply.
FunctionPinNotes
Specications
0VDC(-)
1
0VDC
DCinput
2
ForpoweringcontrollerwhennotusingPowerover
Ethernet.
Note:Thispincanonlybeusedaspowerin.
10–30VDC,max26W,
Maxloadonoutputs=14W
NetworkConnector
RJ45Ethernetconnector.SupportsPoweroverEthernet(PoE).
WhenusedinsystemsthatrequireULcertication,theproductshallbeconnectedtoUL
294B-listednetworkequipment.
50