7.2 Logbooks
1 Classification of logbook entries
The entries are distinguished into three classes and identified by the initial character in the
first line.
"I"information
"W"warning
"E"error/ malfunction
2 Type of occurrence
"+"point of time identifying the beginning of a status
"-"point of time identifying the end of a status
7.2.1 Overview of event entries in meter logbooks
Message No.
on LCD
Details Logbook LCD Text
Custody logbook [1]
3002
NO DSP communication
1
E+System 0001
NO DSP-Communic.
E-System 0001
NO DSP-Communic.
3003 Measurement invalid 1
E+DSP 0001
Reading invalid
E-DSP 0001
Reading invalid
3004 Firmware CRC invalid 1
E+Firmware 0001
CRC invalid
E-Firmware 0001
CRC invalid
3005 Parameter CRC invalid 1
E+Parameter 0001
CRC invalid
E-Parameter 0001
CRC invalid
3006 Parameter out of range 1
E+Parameter 0001
#XXXX range error
E-Parameter 0001
#XXXX range error
3007
Failure during storage of path compensation
parameter
1
E+PathComp. 0001
Storage error
E+PathComp. 0001
Storage error
3008 Meter clock time invalid 1
E+System 0001
ClockTime inval.
E-System 0001
ClockTime inval.