Installation guide
3015‐5543
Revision0
12
/14/10
Installation Guide
Bacharach HGM-MZ to LonWorks FT-10
Communications Adapter
NOTE: User resource files are available for download on the Bacharach web site.
Introduction
The Bacharach HGM-MZ to LonWorks FT-10 Communications Adapter enables a Bacharach
HGM-MZ Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network. Zone
PPM readings, flow status, refrigerant selections, and HGM-MZ internal health may be viewed over
LonWorks. In addition, each HGM-MZ zone supports three levels of alarming (leak, spill, and
evacuate) and each alarm threshold can be set over LonWorks.
Figure 1 – HGM-MZ-to-LonWorks FT-10 Communications Adapter
The LonWorks FT-10 Communications Adapter can be used in conjunction with the MZ-RD remote
display if desired. Wiring details and operational limitations when using the MZ-RD are discussed
below. For additional information on the Bacharach HGM-MZ, refer to document 3015-5074.
CAUTION:
The adapter is powered from the 120/240V universal power supply connection on the
HGM-MZ main board. 120/240V is present on the lower left corner of this adapter
within the area shown on the board silkscreen. Keep fingers away from this area when
the HGM-MZ is powered.
Page1of13