Specifications

M GD-100 M anual
24 6109-9000 Rev 3
IMPORTANT: Ensure that connections 1 to 4 on the sensor
connect to their corresponding numbers on the termi nal block
in the mai n control unit, otherwise it could c ause damage to the
MGD-100.
NOT E: You may use different cables and longer distances
provided t he corresponding resistance shown above is not
exceeded.
4.2. External Audible Alarm and DC Output
NOT E: This section applies to the external audible alarm and
the 12 VDC output (4-6 channel systems only).
Step Wiring the External Audible Alarm and DC Output
1
To install the audible alarm, connect positive lead to CN9
terminal (for one-alarm models) or CN11 terminal (for two-
alarm models ) marked +12V.
2 Connect the negative to the center terminal marked ‘BUZZ’.
3
The 12 VDC/ 100 mA output is obtained via CN9/ CN11
terminals ‘+12V’ and ‘0V. This output may be wired via the
relays to obtain a switching 12 VDC output to drive an
external relay or solenoid.
NOT E: If both the buzzer and 12V DC output are
connected correctly,
they should not exceed
250 mA in total.
4
Connect terminal+12V’ on CN9/CN11 to the ‘COM terminal
of the relay and the device to be switched to eit her the N/O or
N/C termi nal (depending on whether a 12V out put is required
during an alarm condition or while the system is on standby).
5
The return from the device is connected to Ze ro on
CN9/CN11.