Specifications
M GD-100 M anual
6109-9000 Rev 3 35
CAUTION: Before you carry out the bump test or calibration:
• Advise occupants, plant operators, and supervisors.
• Check if the MGD-100 is connected to external systems
such as sprinkler systems, plant s hut down, external
sirens and beacons, ventilation, etc. and disconnect as
instructed by the customer.
• For one-alarm systems you should deacti vat e the 3-min
alarm delay (if selected) by moving jum per JP1 to the
“off” position.
• Ideally, for bump t est or calibration the MGD-100 should
be powered up overnight. See Section 5 for more
information.
6.2. Electrical Reset of One-Alarm Systems
Reset, if necessary, the Standby and Alarm Threshold Voltage to the
factory settings as shown on the calibration label. Electrical res et
information is listed on the label on the side of the enclosure and is
unique to that sensor. Two adj ustments are required and they are
performed on the MGD-100 controller unit.
NOT E: If the sensor standby voltage (SSV) is greater than
the alarm threshold voltage, as in when a gas leak occurs,
then an alarm condition occurs (red LED, siren, relay
operates).
If the SSV falls below 0.18 V, a fault condition will be shown
on the controller (red LED, no siren, relay does not operate).
Tools required:
• A voltmeter (crocodile clips recommended)
• Factory set point electric values (as shown on the rating label)
• Screwdri ver (depending on enclosure).
Step Electrical Re set of One-Alarm Systems
1
First disable the 3-minute alarm delay by movi ng the jumper
link at JP1 to the “OFF” position. See Figure 13 and Fi gure
15.










