Specifications
M GD-100 M anual 
38  6109-9000 Rev 3 
Step  Bump Testing U si n g Calibration Gas Cylinders 
1 
Remove the enclosure lid of the gas sensor and controller 
(not applicabl e to Exd Remote sensor and vent pipe model 
as monitoring of voltage can be done on controller).  
2 
Connect the voltmeter to the channel under test between Pin 
4 and Pin 2 (for single-l evel alarm units), or TP5 and TP 4 (for 
dual-alarm units), to monitor sensor response.  
3 
Expose the sensor to gas from the cylinder by using a plastic 
hose/hood to di rect gas to the sensor head.  
Figure 17. Gas Cylinder and Test Hardware 
NOT E: If the bump test is unsuccessful, perform a 
calibration as described later in this manual. 
IMPORTANT: A fter a semiconductor sensor is exposed to a 
substantial gas leak, the  sensor should be checked and 
replaced if necessary.  
Gas ampoules are convenient and inexpensive alternatives to using gas 
cylinders for bump testing. 










