Specifications
M GD-100 M anual 
40  6109-9000 Rev 3 
Step  Bump Testing Using Ga s Ampoule s 
9 
Remove the beaker from the sensor. Carefully remove any 
ampoule remains from the gas detector and beaker. 
6.5. Calibration Overview 
To comply with t he requirements of EN378 and t he E uropean F-GAS  
regulation, sensors must be tested annually. However, local regulations 
may specify the nature and frequency of this test. 
CAUTION: Check local regulations on c alibration or t esting 
requirements.  
6.6.  Calibration Options 
There are two available calibration options:  
•  Exchanging the sensor board  for a new, pre-calibrated one and 
send old one to B acharach for rec alibration (available for two-
alarm units and 1- and two-alarm IR units) 
•  On-site gas calibration. 
These are explained in the next two sections. 
6.7.  Sensor Board Exchange 
There are a number of advantages to sensor board exchange. It  is 
simpler and quicker than gas calibration. 
NOT E: S ensor board exchange is available for t wo-alarm 
semiconductor (SC) units and  one-  and two-alarm 
infrared 
(IR) units. 
NOT E: Bacharach recommends exchangi ng your sensor 
PCB for a new pre-calibrated one every 3 years.  
Tools required:  
•  A pre-cali brated sensor board 
•  A voltmeter (crocodile clips recommended) 