Installation guide

3015-4570
Revision 1.1
8/6/03
Installation Guide
Bacharach HGM300 to Johnson Metasys N2
Communications Adapter
Electrically Isolated N2 Port Version
Introduction
The Bacharach HGM300 to Johnson Metasys N2 Communcations Adapter enables an
HGM300 Refrigerant Monitor to communicate with a Metasys building management
system. Zone PPM readings, flow status, refrigerant selections, and HGM internal health
may be viewed on Metasys operator stations. In addition, each HGM zone supports three
levels of alarming (Leak, Spill, Evacuate) through Metasys and each alarm threshold can
be set through Metasys.
The N2 Communications Adapter can be used in conjunction with the RDM800 remote
display if desired. Wiring details and operation limitations when using the RDM800 will
be discussed below.
Caution
The adapter is powered from the 120V Auxiliary Power connection on the HGM main
board. When the HGM is powered up, 120V is present on the lower left corner of the
adapter within the area shown on the board silkscreen. Keep fingers away from this area
when HGM is powered!!
Adapter Installation Inside HGM300
The communications adapter board will normally be installed in the HGM300 at the
factory. It can, however, be field installed by following the instructions below.
The following installation materials are needed for field installation of the adapter:
(5) 6-32 x ¼” screws (standard finish)
(5) 6-32 x ½” threaded standoffs
(5) 6-32 x ¼” decorative black anodized screws (standard finish OK, black looks nicer)