User`s manual

Power supply modules Part names
7 – 6
Q63RP and Q64RP
Fig. 7-2: Part names of power supply modules Q63RP and Q64RP
No. Name Application
POWER LED Operation indication:
ON (green): Normal operation (5 V DC output)
ON (red): DC power is input but the power supply module is faulty (5 V DC
error, overload, or internal circuit failure)
OFF:
DC power not input, power failure (including momentary power failure
longer than the allowable momentary power failure period)
blown fuse
ERR terminal
Error output (max. 24 V, 0.5 A)
When power supply is mounted on redundant power main base unit
(Q3RB): Turns on when the system on the redundant power main base unit
operates normally. Turns off (open) when
the power supply module fails
the DC power supply is not input
a CPU module stop error (including a reset) occurs
or the fuse is blown.
Turns off (open) when a stop error occurs in any of the CPU modules in a mul-
tiple CPU system.
When power supply is mounted on redundant power extension base unit
(Q6RB): Turns on when the power supply module operates normally
Turns off (open) when
the power supply module fails
the DC power supply is not input
or the fuse is blown.
FG terminal Ground terminal connected to the shield pattern of the printed circuit board.
LG terminal Grounding for the power supply filter.
Power input
terminals
Terminals for input voltage of the power supply
Terminal screw M3.5x7
Terminal cover Protective cover of the terminal block
Module fixing screw
hole
Screw hole for securing a module to the base unit.
M3x12 screw (user-prepared)
Module mounting
lever
This spring loaded lever simplifies disassembling of the module from the base
unit.
Tab. 7-7: Description for part names of power supply modules
Q64RP
Q63RP