User`s manual
Wiring Installation
MELSEC System Q, Hardware 9 – 21
Wiring of I/O equipment
● The wires used for connection to the terminal block must be 0.3 to 0.75 mm
2
in core
.
● Run the input and output lines away from each other.
● Do not lay I/O signal cables close to the main circuit and high-voltage power lines. Keep a
safe distance of more than 100 mm from the above.
● When the input and output lines cannot be run away from the main circuit and power lines,
use a batch-shielded cable. Normally the shield of the shielded cable must be grounded on
the module side.
● Where wiring runs through piping, ground the piping.
● Run the 24 V DC input line away from the 110 V AC and 230 V AC lines.
E000318C
Fig. 9-20: Wiring of I/O equipment
NOTE
Wiring of 200 m or longer will raise current leakage due to the line capacity, resulting in a
fault.
PLC
Shielded cable
Input
LOAD
Output
DC