User`s manual

Troubleshooting Error code list
11 – 36
1500
AC DOWN
A momentary power supply interruption has
occurred.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
Check the power supply.
ON OFF Continue
)
1510
SINGLE PS. DOWN
Die Versorgungsspannung eines redundanten
Netzteils auf einem redundanten Baugruppenträ-
ger ist eingebrochen.
Collateral information
Common Information: Base No. / Nr. des
Netzteils
Individual Information: —
Diagnostic Timing
Always
Check the power supplied to the redundant
power supply modules mounted on the redun-
dant base unit.
ON ON Continue Qn(H) (first 5
digits of serial
No. is 04101 or
later)
QnPH (first 5
digits of serial
No. is 04101 or
later)
QnPRH
QnU (except
Q00UJ-, Q00U-
and Q01UCPU)
1520
SINGLE PS. ERROR
Ein redundantes Netzteils auf einem redundanten
Baugruppenträger ist defekt.
Collateral information
Common Information: Base No. / Nr. des
Netzteils
Individual Information: —
Diagnostic Timing
Always
Hardware fault of the redundant power supply
module.
Contact your local Mitsubishi representative.
1600
BATTERY ERROR
The battery voltage in the CPU module has
dropped below stipulated level.
The lead connector of the CPU module battery
is not connected.
Collateral information
Common Information: Drive Name
Individual Information: —
Diagnostic Timing
Always
Change the battery.
If the battery is for program memory, stand-
ard RAM or for the back-up power function,
install a lead connector.
Check the lead connector of the CPU module
for looseness. Firmly engage the connector if
it is loose.
NOTE:
When this error occurs, the BAT. LED of the CPU
module is lit too.
ON OFF Continue
)
1601
BATTERY ERROR
Voltage of the battery on memory card has drop-
ped below stipulated level.
Collateral information
Common Information: Drive Name
Individual Information: —
Diagnostic Timing
Always
Change the battery.
NOTE:
When this error occurs, the BAT. LED of the CPU
module is lit too.
1610
FLASH ROM ERROR]
The number of writing to flash ROM (standard
ROM and system securement area) exceeds
100,000 times.
(Number of writings = 100,000 times max.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When writing to ROM
Change the CPU module.
ON ON Continue QnU
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-3: Error code list (1000 to 1999) for PLC CPUs of MELSEC System Q