User`s manual

Troubleshooting Error code list
11 – 40
2103
SP. UNIT LAY ERR.
Two or more QI60/A1SD51S modules are
mounted in a single CPU system.
Two or more QI60/A1SD51S modules are set
to the same control CPU in a multiple CPU
system.
Two or more A1SD51S modules are loaded in
a multiple CPU system.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Reduce the number of QI60/A1SD51S mod-
ules mounted in the single CPU system to
one.
Change the number of QI60/A1SD51S mod-
ules set to the same control CPU to only one
in the multiple CPU system.
Reduce the number of A1SD51S modules to
only one in the multiple CPU system. When
using an interrupt module with each QCPU in
a multiple CPU system, replace it with the
QI60. (Use one A1SI61 module + max. three
QI60 modules or only the QI60 modules.)
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
SP. UNIT LAY ERR.
Two or more QI60, A1SD51S interrupt modules
have been mounted.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Install only one QI60, A1SD51S module.
Qn(H)
QnPRH
SP. UNIT LAY ERR.
Two or more QI60 modules are mounted.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Install only one QI60 module.
Q00J/Q00/Q01
(first 5 digits of
serial No. is
04101 or later)
SP. UNIT LAY ERR.
Two or more QI60 modules where interrupt
pointer setting has not been made are mounted.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Install only one QI60 module.
Make interrupt pointer setting to the second
QI60 module and later.
Q00J/Q00/Q01
(Function
version is B or
later)
QnU
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q