User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 45
2124
SP. UNIT LAY ERR.
A module is mounted on the 65th slot or later
slot.
A module is mounted on the slot whose
number is greater than the number of slots
specified at [Slots] in [Standard setting] of
the base setting.
A module is mounted on the slot whose
number of I/O points exceeds 4096 points.
A module is mounted on the slot whose
number of I/O points strides 4096 points.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Remove the module mounted on the 65th slot
or later slot.
Remove the module mounted on the slot
whose number is greater than the number of
slots specified at [Slots] in [Standard setting]
of the base setting.
Remove the module mounted on the slot
whose number of I/O points exceeds 4096
points.
Replace the module with the one whose
number of occupied points does not exceed
4096 points.
OFF Flicker Stop Qn(H)
QnPH
QnPRH
QnU (except
Q00UJ-, Q00U-,
Q01U and
Q02UCPU)
SP. UNIT LAY ERR.
A module is mounted on after the 25th slot
(or after the 17th slot for the Q00UJCPU).
A module is mounted on the slot whose
number is later than the one set in the "Base
setting" on the I/O assignment tab of PLC
parameter in GX (IEC) Developer.
A module is mounted on the slot for which I/O
points greater than 1024 (greater than 256 for
the Q00UJCPU) is assigned.
A module is mounted on the slot for which I/O
points is assigned from less than 1024 to
greater than 1024 (from less than 256 to
greater than 256 for the Q00UJCPU).
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Remove the module mounted on after the
25th (or after the 17th slot for the
Q00UJCPU).
Remove the module mounted on the slot
whose number is later than the one set in the
"Base setting" on the I/O assignment tab of
PLC parameter in GX (IEC) Developer.
Remove the module mounted on the slot for
which I/O points greater than 1024 (greater
than 256 for the Q00UJCPU) is assigned.
Replace the end module with the one whose
number of occupied points is within 1024
(within 256 for the Q00UJCPU).
OFF Flicker Stop Q00UJ
Q00U/Q01U
SP. UNIT LAY ERR.
A module is mounted on the 37th slot or later
slot.
A module is mounted on the slot whose
number is greater than the number of slots
specified at [Slots] in [Standard setting] of
the base setting.
A module is mounted on the slot whose
number of I/O points exceeds 2048 points.
A module is mounted on the slot whose
number of I/O points strides 2048 points
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Remove the module mounted on the 37th slot
or later slot.
Remove the module mounted on the slot
whose number is greater than the number of
slots specified at [Slots] in [Standard setting]
of the base setting.
Remove the module mounted on the slot
whose number of I/O points exceeds 2048
points.
Replace the module with the one whose
number of occupied points does not exceed
2048 points.
OFF Flicker Stop Q02U
SP. UNIT LAY ERR.
A module is mounted on the 25th slot or later
slot. (The 17th slot or later slot for the
Q00JCPU.)
A module is mounted on the slot whose
number is greater than the number of slots
specified at [Slots] in [Standard setting] of
the base setting.
A module is mounted on the slot whose
number of I/O points exceeds 1024 points.
(256 points for the Q00JCPU.)
A module is mounted on the slot whose
number of I/O points strides 1024 points.
(256 points for the Q00JCPU.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Remove the module mounted on the 25th slot
or later slot. (The 17th slot or later slot for the
Q00JCPU.)
Remove the module mounted on the slot
whose number is greater than the number of
slots specified at [Slots] in [Standard setting]
of the base setting.
Remove the module mounted on the slot
whose number of I/O points exceeds 1024
points. (256 points for the Q00J.)
Replace the module with the one whose
number of occupied points does not exceed
1024 points. (256 points for the Q00J.) über-
schreitet, gegen eines mit weniger E/As
OFF Flicker Stop Q00J
Q00/Q01
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q