User`s manual
Troubleshooting Error code list
11 – 46
2124
SP. UNIT LAY ERR.
5 or more extension base units were added. (3 or
more base units for Q00JCPU)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Don‘t use more than 4 extension base units (2
extension base units for Q00JCPU).
OFF Flicker Stop Q00J/Q00/Q01
(Version A)
2125
SP. UNIT LAY ERR.
– A module which the QCPU cannot recognise
has been installed.
– There was no response form the intelligent
function module/special function module.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
– Install a usable module
(for MELSEC System Q).
– The intelligent function module/special func-
tion module is experiencing a hardware fault.
OFF Flicker Stop
)
2126
SP. UNIT LAY ERR.
CPU module locations in a multiple CPU system
are either of the following.
– There are empty slots between the QCPU and
QCPU/motion controller.
– A module other than the High performance
model QCPU/Process CPU (including the
motion controller) is mounted on the left-
hand side of the High performance model
QCPU/Process CPU.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information:
Diagnostic Timing
At power ON/ At reset
– Mount modules on the available slots so that
the empty slots will be located on the right-
hand side of the CPU module.
– Remove the module mounted on the left-hand
side of the High performance model QCPU/
Process CPU, and mount the High perform-
ance model QCPU/Process CPU on the empty
slot. Mount the motion CPU on the right-hand
side of the High performance model QCPU/
Process CPU.
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
2128
SP. UNIT LAY ERR.
An unusable module is mounted on the exten-
sion base unit in the redundant system.
Collateral information
Common Information: Module No.
Individual Information:
Diagnostic Timing
At power ON/ At reset
Remove the unusable module from the extension
base unit.
OFF Flicker Stop QnPRH (first 5
digits of serial
No. is 09012 or
later)
2150
SP.UNIT VER. ERR.
In a multiple CPU system, the control CPU of the
intelligent function module incompatible with the
multiple CPU system is set to other than CPU
No.1.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset/At writing to proguram-
mable controller
– Change the intelligent function module for the
one compatible with the multiple CPU system.
– Change the setting of the control CPU of the
intelligent function module incompatible with
the multiple CPU system to CPU No.1.
OFF Flicker Stop Q00J/Q00/Q01
QnPH
QnU (except
Q00UJCPU)
2151
SP. UNIT LAY ERR.
Either of the following modules incompatible
with the redundant system has been mounted in
a redundant system.
CC-Link IE controller network modules
MELSECNET/H modules
Ethernet modules
Collateral information
Common Information: Module No. (Slot No.)
Individual Information:
Diagnostic Timing
At power ON/ At reset/At writing to proguram-
mable controller
Use a module compatible with the redundant
system.
OFF Flicker Stop QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q