User`s manual

Troubleshooting Error code list
11 – 46
2124
SP. UNIT LAY ERR.
5 or more extension base units were added. (3 or
more base units for Q00JCPU)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Don‘t use more than 4 extension base units (2
extension base units for Q00JCPU).
OFF Flicker Stop Q00J/Q00/Q01
(Version A)
2125
SP. UNIT LAY ERR.
A module which the QCPU cannot recognise
has been installed.
There was no response form the intelligent
function module/special function module.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Install a usable module
(for MELSEC System Q).
The intelligent function module/special func-
tion module is experiencing a hardware fault.
OFF Flicker Stop
)
2126
SP. UNIT LAY ERR.
CPU module locations in a multiple CPU system
are either of the following.
There are empty slots between the QCPU and
QCPU/motion controller.
A module other than the High performance
model QCPU/Process CPU (including the
motion controller) is mounted on the left-
hand side of the High performance model
QCPU/Process CPU.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information:
Diagnostic Timing
At power ON/ At reset
Mount modules on the available slots so that
the empty slots will be located on the right-
hand side of the CPU module.
Remove the module mounted on the left-hand
side of the High performance model QCPU/
Process CPU, and mount the High perform-
ance model QCPU/Process CPU on the empty
slot. Mount the motion CPU on the right-hand
side of the High performance model QCPU/
Process CPU.
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
2128
SP. UNIT LAY ERR.
An unusable module is mounted on the exten-
sion base unit in the redundant system.
Collateral information
Common Information: Module No.
Individual Information:
Diagnostic Timing
At power ON/ At reset
Remove the unusable module from the extension
base unit.
OFF Flicker Stop QnPRH (first 5
digits of serial
No. is 09012 or
later)
2150
SP.UNIT VER. ERR.
In a multiple CPU system, the control CPU of the
intelligent function module incompatible with the
multiple CPU system is set to other than CPU
No.1.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset/At writing to proguram-
mable controller
Change the intelligent function module for the
one compatible with the multiple CPU system.
Change the setting of the control CPU of the
intelligent function module incompatible with
the multiple CPU system to CPU No.1.
OFF Flicker Stop Q00J/Q00/Q01
QnPH
QnU (except
Q00UJCPU)
2151
SP. UNIT LAY ERR.
Either of the following modules incompatible
with the redundant system has been mounted in
a redundant system.
CC-Link IE controller network modules
MELSECNET/H modules
Ethernet modules
Collateral information
Common Information: Module No. (Slot No.)
Individual Information:
Diagnostic Timing
At power ON/ At reset/At writing to proguram-
mable controller
Use a module compatible with the redundant
system.
OFF Flicker Stop QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q