User`s manual
Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 57
3012
PAR AME TE R E RROR
Multiple CPU setting or control CPU setting dif-
fers from that of the reference CPU settings in a
multiple CPU system.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN/At writing to
programmable controller
Match the multiple CPU setting or control CPU
setting in the PLC parameter with that of the ref-
erence CPU (CPU No.1) settings.
OFF Flicker Stop Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnU
3013
PAR AME TE R E RROR
In a multiple CPU system, the multiple CPU auto
refresh setting is any of the following:
– When a bit device is specified as a refresh
device, a number other than a multiple of 16
is specified for the refresh-starting device.
– The device specified is other than the one that
may be specified.
– The number of send points is an odd number.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN/At writing to
programmable controller
Check the following in the multiple CPU auto
refresh setting and make correction.
– When specifying the bit device, specify 0 or a
multiple of 16 for the refresh starting device.
– Specify the device that may be specified for
the refresh device.
– Set the number of send points to an even
number.
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
PAR AME TE R E RROR
In a multiple CPU system, the multiple CPU auto
refresh setting is any of the following:
– The total number of transmission points is
greater than the maximum number of refresh
points.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN/At writing to
programmable controller
Check the following in the multiple CPU auto
refresh setting and make correction.
– The total number of transmission points is
within the maximum number of refresh
points.
Q00/Q01
(Function
version is B or
later)
PAR AME TE R E RROR
In a multiple CPU system, the multiple CPU auto
refresh setting is any of the following:
– The device specified is other than the one that
may be specified.
– The number of send points is an odd number.
– The total number of send points is greater
than the maximum number of refresh points.
– The setting of the refresh range crosses over
the boundary between the internal user device
and the extended data register (D) or
extended link register (W).
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN/At writing to
programmable controller
Check the following in the multiple CPU auto
refresh setting and make correction.
– Specify the device that may be specified for
the refresh device.
– Set the number of send points to an even
number.
– Set the total number of send points within the
range of the maximum number of refresh
points.
– Set the refresh range so that it does not cross
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
QnU
(except Q00UJ)
3014
PAR AME TE R E RROR
– In a multiple CPU system, the online module
change parameter (multiple CPU system
parameter) settings differ from those of the
reference CPU 1.
– In a multiple CPU system, the online module
change setting is enabled although the CPU
module mounted does not support online
module change.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN/At writing to
programmable controller
– Match the online module change parameter
with that of the reference CPU 1.
– If the CPU module that does not support
online module change is mounted, replace it
with the CPU module that supports online
module change.
OFF Flicker Stop Qn(H)
QnPH
QnU (except
Q00UJ-, Q00U-,
Q01U- and
Q02UCPU)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-5: Error code list (3000 to 3999) for PLC CPUs of MELSEC System Q