User`s manual
Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 59
3100
LINK PARA. ERROR
In a multiple CPU system, the CC-Link IE con-
troller network module controlled by another
CPU is specified as the head I/O number of the
CC-Link IE controller network module.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN
– Delete the network parameter of the CC-Link
IE controller network module controlled by
another CPU.
– Change the setting to the head I/O number of
the CC-Link IE controller network module
controlled by host CPU.
OFF Flicker Stop Qn(H) (first 5
digits of serial
No. is 09012 or
later)
QnPH (first 5
digits of serial
No. is 10042 or
later)
QnU
LINK PARA. ERROR
The network parameter of the CC-Link IE control-
ler network operating as the normal station is
overwritten to the control station.
Or, the network parameter of the CC-Link IE con-
troller network operating as the control station is
overwritten to the normal station.
(The network parameter is updated on the mod-
ule by resetting.)
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN
Reset the CPU module.
OFF Flicker Stop Qn(H) (first 5
digits of serial
No. is 09012 or
later)
QnPH (first 5
digits of serial
No. is 10042 or
later)
QnPRH (first 5
digits of serial
No. is 10042 or
later)
QnU
LINK PARA. ERROR
– The number of modules actually mounted is
different from that is set in Network parame-
ter for CC-Link IE controller network.
– The head I/O number of the actually mounted
module is different from the one set in the
network parameter of the CC-Link IE control-
ler network.
– Data cannot be handled in the parameter
existing.
– The network type of CC-Link IE controller net-
work is overwritten during power-on. (When
changing the network type, switch RESET to
RUN.)
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN
– Check the network parameters and actual
mounting status, and if they differ, make them
match.
When network parameters are modified, write
them to the CPU module.
– Check the setting of extension base unit stage
number.
– Check the connection status of extension
base unit and extension cables. When the
GOT is busconnected to the main base unit or
extension base unit, also check its connection
status.
If the error occurs even after the above checks,
the possible cause is a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
LINK PARA. ERROR
– The CC-Link IE controller network module is
specified for the head I/O number of network
parameter in the MELSECNET/H.
– The MELSECNET/H module is specified for
the head I/O number of network parameter in
the CC-Link IE controller network.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN
OFF Flicker Stop
LINK PARA. ERROR
– Although the CC-Link IE controller network
module is mounted, network parameter for
the CCLink IE controller network module is
not set.
– Although the CC-Link IE controller network
and MELSECNET/H modules are mounted,
network parameter for the MELSECNET/H
module is not set.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
→
RUN
OFF Flicker Stop
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.