User`s manual

Troubleshooting Error code list
11 – 62
3101
LINK PARA. ERROR
Since the number of points of the B/W device set
in [Device] of the PLC parameter is lower than
the number of B/W refresh device points when
parameters of the MELSECNET/H are not set, the
refresh between the CPU module and the MELS-
ECNET/H cannot be performed.
Number of B/W refresh device points when para-
meters of the MELSECNET/H are not set:
1 network module mounted
B: 8192; W: 8192
2 network modules mounted
B: 8192 (4096x2); W: 8192 (4096x2)
3 network modules mounted
B: 6144 (2048x3); W: 6144 (2048x3)
4 network modules mounted
B: 8192 (2048x4); W: 8192 (2048x4)
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Set the refresh parameter of the MELSECNET/H
in accordance with the number of points of B/W
devices set in [Device] of the PLC parameter.
OFF Flicker Stop Qn(H) (first 5
digits of serial
No. is 09012 or
later)
QnPH (first 5
digits of serial
No. is 09012 or
later)
QnPRH (first 5
digits of serial
No. is 09012 or
later)
QnU
LINK PARA. ERROR
The setting of the network refresh range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Set the network refresh range so that it does not
cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
OFF Flicker Stop
)
3102
LINK PARA. ERROR
A CC-Link IE controller network parameter error
was detected.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Correct and write the network parameters.
If the error occurs after correction, it suggests
a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop Qn(H) (first 5
digits of serial
No. is 09012 or
later)
QnPH (first 5
digits of serial
No. is 10042 or
later)
QnPRH (first 5
digits of serial
No. is 10042 or
later)
QnU
LINK PARA. ERROR
The network module detected a network parame-
ter error.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
OFF Flicker Stop
)
LINK PARA. ERROR
The station No. specified in pairing setting are
not correct.
The stations are not numbered consecutively.
Pairing setting has not been made for the CPU
module at the normal station.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Refer to the troubleshooting of the network mod-
ule, and if the error is due to incorrect pairing
setting, reexamine the pairing setting of the net-
work parameter.
OFF Flicker Stop QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-5: Error code list (3000 to 3999) for PLC CPUs of MELSEC System Q