User`s manual

Troubleshooting Error code list
11 – 64
3103
LINK PARA. ERROR
In a multiple CPU system, Ethernet interface
module under control of another station is speci-
fied to the start I/O number of the Ethernet net-
work parameter.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Delete the Ethernet network parameter of
Ethernet interface module under control of
another station.
Change the setting to the start I/O number of
Ethernet interface module under control of the
host station.
OFF Flicker Stop Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
QnU (except
Q00UJCPU)
LINK PARA. ERROR
Although the number of modules has been set
to one or a greater number in the Ethernet
module count parameter setting, the number
of actually mounted module is zero.
The start I/O No. of the Ethernet network
parameter differs from the I/O No. of the actu-
ally mounted module.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Correct and write the network parameters.
If the error occurs after correction, it suggests
a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
)
LINK PARA. ERROR
Ethernet module whose network type is set to
"Ethernet (main base)" is mounted on the
extension base unit in the redundant system.
Ethernet module whose network type is set to
"Ethernet (extension base)" is mounted on the
main base unit in the redundant system.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Correct and write the network parameters.
If the error occurs after correction, it suggests
a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop QnPRH (first 5
digits of serial
No. is 09012 or
later)
3104
LINK PARA. ERROR
The Ethernet, MELSECNET/H and MELSEC-
NET/10 use the same network number.
The network number, station number or
group number set in the network parameter is
out of range.
The specified I/O number is outside the range
of the used CPU module.
The Ethernet-specific parameter setting is not
normal.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Correct and write the network parameters.
If the error occurs after correction, it suggests
a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-5: Error code list (3000 to 3999) for PLC CPUs of MELSEC System Q