User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 67
3301
SP. PARA. ERROR
The refresh setting of the intelligent function
module exceeded the file register capacity.
The intelligent function module set in GX Con-
figurator differs from the actually mounted
module.
Collateral information
Common Information: File name
Individual Information: Parameter No. (gained
by dividing the head I/O number of parameter
in the intelligent function module set by GX
Configurator by 10
H
)
Diagnostic Timing
At power ON/At reset/STOP
RUN/At writing to
programmable controller
Change the file register file for the one which
allows refresh in the whole range.
Check the parameter setting.
OFF Flicker Stop Q00J/Q00/Q01
Qn(H)
(Function
version is B or
later)
QnPH
QnPRH
QnU
SP. PARA. ERROR
The intelligent function module's refresh para-
meter setting is outside the available range.
Collateral information
Common Information: File name
Individual Information: Parameter No. (gained
by dividing the head I/O number of parameter
in the intelligent function module set by GX
Configurator by 10
H
)
Diagnostic Timing
At power ON/At reset/STOP
RUN/At writing to
programmable controller
Check the parameter setting.
OFF Flicker Stop
)
SP. PARA. ERROR
The setting of the refresh parameter range
crosses over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
Collateral information
Common Information: File name
Individual Information: Parameter No. (gained
by dividing the head I/O number of parameter
in the intelligent function module set by GX
Configurator by 10
H
)
Diagnostic Timing
At power ON/At reset/STOP
RUN/At writing to
programmable controller
Set the refresh parameter range so that it does
not cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
OFF Flicker Stop QnU
3302
SP. PARA. ERROR
The intelligent function module's refresh para-
meter are abnormal.
Collateral information
Common Information: File name
Individual Information: Parameter No. (gained
by dividing the head I/O number of parameter
in the intelligent function module set by GX
Configurator by 10
H
)
Diagnostic Timing
At writing to programmable controller
Check the parameter setting.
OFF Flicker Stop
)
3303
SP. PARA. ERROR
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to
the intelligent function module under control of
another station.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP RUN/At writing to
programmable controller
Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
Change the setting to the automatic refresh
setting or other parameter setting of the intel-
ligent function module under control of the
host CPU.
OFF Flicker Stop Q00J/Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
QnU (except
Q00UJCPU)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-5: Error code list (3000 to 3999) for PLC CPUs of MELSEC System Q