User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 69
11.3.4 Error code list (4000 to 4999)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
4000
INSTRCT CODE. ERR.
The program contains an instruction code
that cannot be decoded.
An unusable instruction is included in the pro-
gram.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN/
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop
)
4001
INSTRCT CODE. ERR.
The program contains a dedicated instruction for
SFC although it is not an SFC program.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN/
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop Q00J/Q00/Q01
(Function
version is B or
later)
Qn(H)
QnPH
QnPRH
QnU
4002
INSTRCT CODE. ERR.
The name of dedicated instruction specified
by the program is incorrect.
The dedicated instruction specified by the
program cannot be executed by the specified
module.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN/
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop
)
4003
INSTRCT CODE. ERR.
The number of devices for the dedicated instruc-
tion specified by the program is incorrect.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN/
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop
)
4004
INSTRCT CODE. ERR.
The device which cannot be used by the dedica-
ted instruction specified by the program is speci-
fied.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN/
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop
)
4010
MISSING END INS.
There is no END (FEND) instruction in the pro-
gram.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP RUN
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF Flicker Stop
)
Tab. 11-6: Error code list (4000 to 4999) for PLC CPUs of MELSEC System Q