User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 71
4101
OPERATION ERROR
The number of setting data dealt with the
instruction exceeds the applicable range.
The storage data and constant of the device
specified by the instruction exceeds the appli-
cable range.
When writing to the host CPU shared mem-
ory, the write prohibited area is specified for
the write destination address.
The range of storage data of the device speci-
fied by the instruction is duplicated.
The device specified by the instruction
exceeds the range of the number of device
points.
The interrupt pointer No. specified by the
instruction exceeds the applicable range.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
)
OPERATION ERROR
The storage data of file register specified by
the instruction exceeds the applicable range.
Or, file register is not set.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
QnU (except
Q00UJCPU)
OPERATION ERROR
Block data that crosses over the boundary
between the internal user device and the
extended data register (D) or extended link regis-
ter is specified (including 32-bit binary, real
number (single precision, double precision),
indirect address, and control data).
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
QnU
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-6: Error code list (4000 to 4999) for PLC CPUs of MELSEC System Q