User`s manual

Troubleshooting Error code list
11 – 72
4102
OPERATION ERROR
In a multiple CPU system, the link direct device
(J\), was specified for the network module
under control of another station.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Delete from the program the link direct device
which specifies the network module under
control of another CPU.
Using the link direct device (J\), specify
the network module under control of the host
CPU.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
QnU (except
Q00UJCPU)
OPERATION ERROR
The network No. or station No. specified for
the dedicated instruction is wrong.
The link direct device (J\) setting is incor-
rect.
The module No./ network No./number of
character strings exceeds the range that can
be specified.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
)
OPERATION ERROR
The specification of character string (" ") speci-
fied by dedicated instruction cannot be used for
the character string.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
QnU
4103
OPERATION ERROR
The configuration of the PID dedicated instruc-
tion is incorrect.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Read the common information of the error using
GX (IEC) Developer, check error step corre-
sponding to its numerical value (program error
location), and correct the problem.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
Q00J/Q00/Q01
(Function
version is B or
later)
Qn(H)
QnPRH
QnU
4105
OPERATION ERROR
PLOADP/PUNLOADP/PSWAPP instructions were
executed while setting program memory check.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Delete the program memory check setting.
When using the program memory check,
delete PLOADP/PUNLOADP/PSWAPP instruc-
tions.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
QnPH (first 5
digits of serial
No. is 07032 or
later)
4107
OPERATION ERROR
33 or more multiple CPU dedicated instructions
were executed from one CPU module.
Collateral information
Common Information: Program error location
Individual Information: —
Diagnostic Timing
When instruction executed
Using the multiple CPU dedicated instruction
completion bit, provide interlocks to prevent one
CPU module from executing 33 or more multiple
CPU dedicated instructions.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
Q00U/Q01U/
Q02U
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-6: Error code list (4000 to 4999) for PLC CPUs of MELSEC System Q