User`s manual

Troubleshooting Error code list
11 – 86
6030
UNIT LAY. DIFF.
In a redundant system, the module configura-
tion differs between the control system and
standby system.
The network module mode setting differs
between the two systems.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: Module No.
Individual Information: —
Diagnostic Timing
At power ON/At reset/At tracking cable connec-
tion/At operation mode change
Match the module configurations of the con-
trol system and standby system.
In the redundant setting of the network
parameter dialog box, match the mode setting
of System B to that of System A.
OFF Flicker Stop QnPRH
6035
UNIT LAY. DIFF.
In a redundant system, the CPU module model
name differs between the control system and
standby system.
(This can be detected from the standby system
of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset/At tracking cable connec-
tion/At operation mode change
Match the model names of the control system
and standby system.
OFF Flicker Stop QnPRH
6036
UNIT LAY. DIFF.
A difference in the remote I/O configuration of
the MELSECNET/H multiplexed remote I/O net-
work between the control system and standby
system of a redundant system was detected.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: Module No.
Individual Information: —
Diagnostic Timing
Always
Check the network cables of the MELSECNET/H
multiplexed remote I/O network for disconnec-
tion.
OFF Flicker Stop QnPRH
6040
CARD TYPE DIFF.
In a redundant system, the memory card instal-
lation status (installed/not installed) differs
between the control system and standby system.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset
Match the memory card installation statuses
(installed/not installed) of the control system and
standby system.
OFF Flicker Stop QnPRH
6041
CARD TYPE DIFF.
In a redundant system, the memory card type
differs between the control system and standby
system.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset
Match the memory card types of the control sys-
tem and standby system.
OFF Flicker Stop QnPRH
6050
CAN'T EXE. MODE.
The function inexecutable in the debug mode or
operation mode (backup/separate mode) was
executed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
Execute the function in the debug mode or oper-
ation mode (backup/separate mode).
ON ON Continue QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-8: Error code list (6000 to 6999) for PLC CPUs of MELSEC System Q