User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 87
6060
CPU MODE DIFF.
In a redundant system, the operation mode
(backup/separate) differs between the control
system and standby system.
(This can be detected from the standby system
of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset/At tracking cable connec-
tion/
Match the operation modes of the control sys-
tem and standby system.
OFF Flicker Stop QnPRH
6061
CPU MODE DIFF.
In a redundant system, the operation mode
(backup/separate) differs between the control
system and standby system.
(This can be detected from the standby system
of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When an END instruction executed
Match the operation modes of the control sys-
tem and standby system.
OFF Flicker Stop QnPRH
6062
CPU MODE DIFF.
Both System A and B are in the same system sta-
tus (control system).
(This can be detected from the system B of the
redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset/At tracking cable connec-
tion/
Power the CPU module (System B) which
resulted in a stop error, OFF and then ON.
OFF Flicker Stop QnPRH
6100
TRK. TRANS. ERR.
An error (e.g. retry limit exceeded) occurred
in tracking data transmission.
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6101
TRK. TRANS. ERR.
A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-8: Error code list (6000 to 6999) for PLC CPUs of MELSEC System Q