User`s manual

Troubleshooting Error code list
11 – 88
6102
TRK. TRANS. ERR.
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6103
TRK. TRANS. ERR.
A data error (other than sum value error)
occurred in tracking (data reception).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6105
TRK. TRANS. ERR.
An error (e.g. retry limit exceeded) occurred
in tracking (data transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system
or standby system of the redundant system.)
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6106
TRK. TRANS. ERR.
A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6107
TRK. TRANS. ERR.
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-8: Error code list (6000 to 6999) for PLC CPUs of MELSEC System Q