6102
TRK. TRANS. ERR.
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
– Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6103
TRK. TRANS. ERR.
– A data error (other than sum value error)
occurred in tracking (data reception).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
– The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
– Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6105
TRK. TRANS. ERR.
– An error (e.g. retry limit exceeded) occurred
in tracking (data transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
– The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system
or standby system of the redundant system.)
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
– Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6106
TRK. TRANS. ERR.
– A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
– The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: Tracking transmission
data classification
Individual Information: —
Diagnostic Timing
Always
– Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
6107
TRK. TRANS. ERR.
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
– Check the CPU module or tracking cable. If
the error still occurs, this indicates the CPU
module or tracking cable is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
ON ON Continue QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-8: Error code list (6000 to 6999) for PLC CPUs of MELSEC System Q