User`s manual
Troubleshooting Error code list
11 – 94
7010
MULTI EXE. ERROR
– In a multiple CPU system, a faulty CPU mod-
ule was mounted.
– In a multiple CPU system, a CPU module
incompatible with the multiple CPU system
was mounted. (The CPU module compatible
with the multiple CPU system was used to
detect an error.)
– In a multiple CPU system, any of the CPU No.
2 to 4 was reset with power ON. (The CPU
whose reset state was cancelled was used to
detect an error.)
Collateral information
Common Information: Module No. (CPU No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
– Read the individual information of the error
using GX (IEC) Developer, and replace the
faulty CPU module.
– Replace the CPU module with the one com-
patible with the multiple CPU system.
– Do not reset any of the No. 2 to 4 CPU mod-
ules.
– Reset CPU No. 1 and restart the multiple CPU
system.
OFF Flicker Stop Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
QnU (except
Q00UJCPU)
MULTI EXE. ERROR
The PC CPU module-compatible software pack-
age (PPC-DRV-01) whose version is 1.06 or ear-
lier is used in a multiple CPU system.
Collateral information
Common Information: Module No. (CPU No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Change the version of the PC CPU module-com-
patible software package (PPC-DRV-01) to 1.07
or later.
Q00/Q01
(Function
version is B or
later)
MULTI EXE. ERROR
The Q172(H)CPU(N) or Q173(H)CPU(N) is
mounted on the multiple CPU high-speed main
base unit (Q3DB).
(This may result in a module failure.)
Collateral information
Common Information: Module No. (CPU No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Replace the Q172(H)CPU(N) and
Q173(H)CPU(N) with the Motion CPU compati-
ble with the multiple CPU high-speed main base
unit.
Qn(H) (first 5
digits of serial
No. is 09082 or
later)
QnPH (first 5
digits of serial
No. is 09082 or
later)
MULTI EXE. ERROR
The Universal model QCPU (except Q02UCPU)
and Q172(H)CPU(N) are mounted on the same
base unit.
(This may result in a module failure.)
Collateral information
Common Information: Module No. (CPU No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Check the QCPU and Motion CPU that can be
used in a multiple CPU system, and change the
system configuration.
Qn(H) (first 5
digits of serial
No. is 09082 or
later)
QnPH (first 5
digits of serial
No. is 09082 or
later)
7011
MULTI EXE. ERROR
Either of the following settings was made in a
multiple CPU system.
– Multiple CPU automatic refresh setting was
made for the inapplicable CPU module.
– "I/O sharing when using multiple CPUs" set-
ting was made for the inapplicable CPU mod-
ule.
Collateral information
Common Information: Module No. (CPU No.)
Individual Information: —
Diagnostic Timing
At power ON/ At reset
Correct the settings.
OFF Flicker Stop Q00/Q01
(Function
version is B or
later)
QnU (except
Q00UJCPU)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.