User`s manual
Input/output module specifications Specifications
MELSEC System Q, Hardware 12 – 9
12.3.2 Digital input module QX10-TS
Item QX10-TS
Number of input points 16
Isolation method Photocoupler
Rated input voltage 110–120 V AC (+10/–15 %), 50/60 Hz (
±
3 Hz), distortion within 5 %
Rated input current approx. 7 mA (at 100 V AC, 50 Hz); approx. 8 mA (at 100 V AC, 60 Hz)
Max. simultaneously ON Refer to the derating chart
Inrush current max. 200 mA within 1 ms (at 132V AC)
ON voltage/ON current
≥
80 V AC /
≥
5 mA (50 Hz / 60 Hz)
OFF voltage/OFF current
≤
30 V AC /
≤
1 mA (50 Hz / 60 Hz)
Input impedance approx. 15 k
Ω
at 50 Hz, approx. 12 k
Ω
at 60 Hz
Response time
OFF
→
ON
≤
15 ms (100 V AC, 50 Hz / 60 Hz)
ON
→
OFF
≤
20 ms (100 V AC, 50 Hz / 60 Hz)
Groups of input 1; 16 points/common
(common terminal: 17)
Input status display One LED per input
Dielectric withstand voltage 1780 V AC rms/3 cycles (altitude 2000 m)
External connections Removable terminal block with spring terminals
Applicable wire size
Core cable 0.3 to 2.0 mm
2
, (outside diameter: 1.45 mm max.)
Internal current consumption
(5 V DC)
50 mA (all input points ON)
Weight 0.17 kg
External connections
Terminal
block
number
Signal
1X00
2X01
3X02
4X03
5X04
6X05
7X06
8X07
9X08
10 X09
11 X0A
12 X0B
13 X0C
14 X0D
15 X0E
16 X0F
17 COM
18 Vacant
Tab. 12-9: Input module QX10-TS
QH00032C
Fig.12-2:
QX10-TS Derating chart
Internal
circuit
Input module
1
16
17
100–120 V AC
LED
100
90
80
70
60
50
40
0102030
40 50 55
120 V AC
132 V AC
%
[C]
°
Ambient temperature
ON ratio