User`s manual

Input/output module specifications Specifications
MELSEC System Q, Hardware 12 – 19
12.3.10 Digital input module QX42-S1
Response time setting by parameters. Initial setting: 0.2 ms
Item QX42
Number of input points 64
Isolation method Photocoupler
Rated input voltage 24 V DC (+20/–15 %, ripple ratio within 5 %)
Rated input current approx. 4 mA
Max. simultaneously ON Refer to the derating chart
Inrush current
ON voltage/ON current
19 V DC /
3 mA
OFF voltage/OFF current
9.5 V DC /
1.5 mA
Input impedance approx. 5.6 k
Ω
Response
time
Set value
0.1 ms 0.2 ms 0.4 ms 0.6 ms 1 ms
OFF
ON typ. 0.05 ms 0.15 ms 0.30 ms 0.55 ms 1.05 ms
max. 0.10 ms 0.20 ms 0.40 ms 0.60 ms 1.20 ms
ON
OFF typ. 0.15 ms 0.20 ms 0.35 ms 0.60 ms 1.10 ms
max. 0.2 ms 0.30 ms 0.50 ms 0.70 ms 1.30 ms
Groups of input 2; 32 points/common
(common terminal: 1B01/1B02 and 2B01/2B02)
Input status display One LED per input of a group, Groups are switchable
Dielectric withstand voltage 560 V AC rms/3 cycles (altitude 2000 m)
External connections Two 40-pin connectors
Applicable wire size
0.3 mm
2
Accessories
Connector A6CON
Assembled cable Q40-CBL-3M/5M with 40 pin plug
Internal current consumption
(5 V DC)
90 mA (all input points ON)
Weight 0.18 kg
External connections
Tab. 12-18: Input module QX42-S1
Internal
circuit
LED
1B01
1B02
1A05
24 V DC
Indication selector switch
Used to switch the LED
indications:
F: Inputs X00 to X1F
L: Inputs X20 to X3F
F
L
Input module
1B20
LED