User`s manual
Input/output module specifications Specifications
MELSEC System Q, Hardware 12 – 33
12.3.20 Relay output module QY10-TS
Item QY10-TS
Number of outputs 16
Isolation method Relay
Rated switching voltage, current 24 V DC, 2 A (resistive load) per output, 220 V AC, 2 A (cos
ϕ
= 1) per output
8 A/group
Minimum switching load 5 V DC, 1 mA
Maximum switching load 264 V AC, 125 V DC
Response time OFF
→
ON
≤
10 ms
ON
→
OFF
≤
12 ms
Life
Mechanical 20 million times or more
Electrical
Rated switching voltage/current load; 100 thousand times or more
200 V AC, 1.5 A; 240 V AC, 1 A (cos
ϕ
= 0.7) 100 thousand times or more
200 V AC, 0.4 A; 240 V AC, 0.3 A (cos
ϕ
= 0.7) 300 thousand times or more
200 V AC, 1 A; 240 V AC, 0.5 A (cos
ϕ
= 0.35) 100 thousand times or more
200 V AC, 0.3 A; 240 V AC, 0.15 A (cos
ϕ
= 0.35) 300 thousand times or more
24 V DC, 1 A; 100 V DC, 0.1 A (L/R = 7 ms) 100 thousand times or more
24 V DC, 0.3 A; 100 V DC, 0.03 A (L/R = 7 ms) 300 thousand times or more
Maximum switching frequency 3600 times/hour
Surge suppressor —
Fuse —
Groups of outputs 1; 16 points/common,
(common terminal: 17)
Output status display One LED per output
Dielectric withstand voltage 2830 V AC rms/3 cycles (altitude 2000 m)
External connections Removable terminal block with spring terminals
Applicable wire size
Core cable: 0.3 to 2.0 mm
2
(outside diameter: 1.45 mm max.)
Internal current consumption
(5 V DC)
430 mA (all output points ON)
Weight 0.22 kg
Tab. 12-33: Relay output module QY10-TS
External connections
Terminal block
number
Signal
1Y00
2Y01
3Y02
4Y03
5Y04
6Y05
7Y06
8Y07
9Y08
10 Y09
11 Y0A
12 Y0B
13 Y0C
T4 Y0D
15 Y0E
16 Y0F
17 COM
18 NC
Tab. 12-34: Relay output module QY10-TS connections
Internal
circuit
1
16
17
LED
100 V AC