User`s manual

Input/output module specifications Specifications
MELSEC System Q, Hardware 12 – 37
12.3.24 Transistor output module QY40P-TS
Sink type
Item QY40P-TS
Number of outputs 16
Isolation method Photocoupler
Rated load voltage 12–24 V DC (+20/–15 %)
Maximum load current 0.1 A per output, 1.6 A per module
Maximum inrush current 0.7 A, 10 ms or less
Leakage current at OFF
0.1 mA
Maximum voltage drop at ON
0.2 V at 0.1 A
Response time
OFF
ON
1 ms
ON
OFF
1 ms (rated load, resistive load)
Surge suppressor Zener Diode
Fuse
Protection function Thermal and overload protections
Thermal/overload protection is activated in units of 1 point
Groups of outputs 1; 16 points/common,
(common terminal: 18)
Output status display One LED per output
Dielectric withstand voltage 560 V AC rms/3 cycles (altitude 2000 m)
External connections Removable terminal block with spring terminals
Applicable wire size
Core cable: 0.3 to 2.0 mm
2
(outside diameter: 1.45 mm max.)
External power
supply
Voltage 12–24 V DC (+20/–15 %, ripple ratio within 5 %)
Current 10 mA (at 24 V DC; all output points ON)
Internal current consumption
(5 V DC)
65 mA (all output points ON)
Weight 0.16 kg
Tab. 12-41: Transistor output module QY40P-TS
External connections
Terminal block
number
Signal
1Y00
2Y01
3Y02
4Y03
5Y04
6Y05
7Y06
8Y07
9Y08
10 Y09
11 Y0A
12 Y0B
13 Y0C
14 Y0D
15 Y0E
16 Y0F
17 12/24 V DC
18 COM
Tab. 12-42: Transistor output module QY40P-TS connections
Internal
circuit
1
LED
12/24 V DC
16
17
18
+