Specifications Input/output module specifications
12 – 46
12.3.32 Transistor output module QY80-TS
Source type
The fuses inside the output module are unchangeable. They protect the external peripherals, if there occurs a
short circuit in the module. The output module itself has no overload protection.
Item QY80-TS
Number of outputs 16
Isolation method Photocoupler
Rated load voltage 12–24 V DC (+20/–15 %)
Maximum load current 0.5 A per output, 4 A per group
Maximum inrush current 4 A, 10 ms or less
Leakage current at OFF
≤
0.1 mA
Maximum voltage drop at ON
≤
0.3 V at 0.5 A
Response time
OFF
→
ON
≤
1 ms
ON
→
OFF
≤
1 ms (rated load, resistive load)
Surge suppressor Zener Diode
Fuse
Two fuses 4 A parallel (nominal fuse current = 6.7 A), unchangeable
Fuse blow indication LED indicates it and signal is output to CPU
Groups of outputs
1; 16 points/common,
(common terminal: 17)
Output status display One LED per output
Dielectric withstand voltage 560 V AC rms/3 cycles (altitude 2000 m)
External connections Removable terminal block with spring terminals
Applicable wire size
Core cable: 0.3 to 2.0 mm
2
(outside diameter: 1.45 mm max.)
External power
supply
Voltage 12–24 V DC (+20/–15 %, ripple ratio within 5 %)
Current 20 mA (at 24 V DC, all output points ON)
Internal current consumption (5 V
DC)
80 mA (all output points ON)
Weight 0.17 kg
Tab. 12-58: Transistor output module QY80-TS
External connections
Terminal block
number
Signal
1Y00
2Y01
3Y02
4Y03
5Y04
6Y05
7Y06
8Y07
9Y08
10 Y09
11 Y0A
12 Y0B
13 Y0C
14 Y0D
15 Y0E
16 Y0F
17 COM
18 0 V
Tab. 12-59: Transistor output module QY80-TS connections
Internal
circuit
1
LED
16
12/24 V DC
17