Specifications Power supply module specifications
12 – 54
12.4 Power supply module specifications
Power supply modules Q61P-A1, Q61P-A2, Q61P, Q61P-D and Q61SP
When power is switched on again immediately (within 5 seconds) after power-off, an inrush current of more than
the specified value (2 ms or less) may flow.
Reapply power 5 or more seconds after power-off.
When selecting a fuse and breaker in the external circuit, take account of the blowout, detection characteristics
etc.
Overcurrent protection
The overcurrent protection device shuts off the 5 V, 24 VDC circuit and stops the system if the current flowing in
the circuit exceeds the specified value.
The LED of the power supply module turns off or turns on in dim green when voltage is lowered. If this device is
activated, switch the input power supply off and eliminate the cause such as insufficient current capacity or short.
Then, a few minutes later, switch it on to restart the system.
Item Q61P-A1 Q61P-A2 Q61P Q61P-D Q61SP
Mounting position Power supply module mounting slot "POWER"
Applicable base unit Q3
B, Q3
DB, Q6
BQ3
SB
Input power sup-
ply
V AC
(+10 %, –15 %)
100 to 120 200 to 240 100 to 240 100 to 240 100 to 240
V DC
(+30 %, –35 %)
—————
Input frequency 50/60 Hz (
±
5 %)
Maximum input apparent power 105 VA 105 VA 120 VA 130 VA 40 VA
Inrush current
20 A within 8 ms
Rated output cur-
rent
5 V DC6 A6 A6 A6 A2 A
24 V DC—————
External output voltage —————
Overcurrent pro-
tection
5 V DC
6.6 A
2.2 A
24 V DC
Overvoltage protection
5.5 to 6.5 V
Efficiency
70 %
Dielectric withstand voltage
(Across primary and secondary
connection)
2830 V AC, 1 min
Operation indication The "POWER" LED turns on in green, when the output voltage is present.
Contact output
section
Application Error contact (refer to chapter 7)
Rated switching
voltage, current
24 V DC; 0.5 A
Minimum
switching load
5 V DC; 1 mA
Response time OFF
ON:
10 ms
ON
OFF:
12 ms
Life Mechanical: More than 20 million times
Electrical: More than 100 thousand times at rated switching voltage, current
Overvoltage
protection
Fuse The signal output is not protected by fuse.
Terminal screw size M3.5x7 M3.5x7
Applicable tightening torque 66 to 89 Ncm
Applicable wire size
0.75 to 2 mm
2
External dimensions (HxWxD) [mm] 98x55.2x90 98x27.4x104
Weight 0.31 kg 0.31kg 0.40 kg 0.45 kg 0.18 kg
Allowable momentary power failure
period
20 ms
Tab. 12-67: Power supply module specifications (1)