User`s manual

Part names and settings of Qn(P)(R)(H)CPUs CPU modules
MELSEC System Q, Hardware 4 – 23
No. Name Application
POWER LED Power indicator LED for 5 V DC. Turns on in green during normal output of
5 V DC.
RUN LED Indicates the operating status of the CPU module.
ON: During operation with the RUN/STOP/RESET switch set to "RUN".
Executes sequence program operation.
OFF: During stop with the RUN/STOP/RESET switch set to "STOP".
When an error that stops operation is detected.
FLICKER: When parameters/program is written during STOP and the RUN/
STOP/RESET switch is moved from "STOP" to "RUN". The CPU is not in
"RUN" mode.
To turn on the RUN LED after writing the program/parameters, perform the fol-
lowing operations.
- Perform reset with the RUN/STOP/RESET switch.
- Set the RUN/STOP/RESET switch from "STOP" to "RUN".
To turn on the RUN LED after writing the program/parameters without per-
forming a reset, perform the following operation:
- Set the RUN/STOP/RESET switch from "STOP" to "RUN" to "STOP" to
"RUN".
ERR. LED Error indication
ON: When the self-diagnostic error that will not stop operation is detected
(continuation of operation at error detection must be set in the parameter).
OFF: Normal
FLICKER: When an error is detected that stops operation.
Base mounting hole This hole is for fixing the Q00JCPU with a screw.
Battery Backup battery for use of the program memory, standard RAM, clock function
and backup power time function.
Battery connector
pin
For connection of the battery lead wires.
Lead wires are disconnected from the connector when shipping to prevent the
battery from consuming.
RUN/STOP/RESET
switch
RUN: Executes sequence program operation.
STOP: Stops sequence program operation.
RESET: Performs hardware reset, operation error reset, operation initializa-
tion or like.
RS232 connector Connector for connecting a programming device (peripheral device) by RS232.
Tab. 4-13: Part names of Q00JCPU