Technical data
Fan Coil Thermostat
Specification & Installation Instructions
TFCB24F3XYZ1-121112-ESA.doc 1
Fan Coil Thermostat with BACnet
®
Communication Port
Technical Data
TFCB24F3XYZ1
Inputs
1 Digital input (24 Vac or dry contact)
1 Analog input (external temperature sensor 10K)
1 Analog input (change over 10K or dry contact)
Outputs
1 Fan analog or 3 Fan speed dry contracts 24 Vac, 1A max 3A in-rush
2 Analog outputs (cooling and/or heating 0-10Vdc)
1 Analog output (local reheat 0-10Vdc )
2 Triacs output (cooling and/or heating) 24 Vac, 0.3A max fused / triac
1 Triac output (local reheat) 24 Vac, 0.3A max fused / triac
Power supply
22 to 26 Vac 50/60Hz
Power consumption
1 VA max
Set point range
10ºC to 40ºC [50ºF to 104ºF]
Control accuracy
Temperature: ±0.4ºC [0.8ºF]
Proportional band
0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent)
Dead band
0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent)
Electrical connection
0.8 mm
2
[18 AWG] minimum
Operating temperature
0ºC to 50ºC [32ºF to 122ºF]
Storage temperature
-30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity
5 to 95 % non condensing
Degree of protection of housing
IP 30 (EN 60529)
Weight 160 g. [0.36 lb]
Dimensions
A = 2.85 in (73mm)
B = 4.85 in (123mm)
C = 1.00 in (24mm)
D = 2.36 in (60mm)
E = 3.27 in (83mm)
A
B
C
D
E
Interface
C
F
%RH
MO TU WE TH FR SA SU
AM
PM
.
.
.
.
Symbols on display
Cooling ON
A: Automatic
Communication
Status
Alarm status
Heating ON
A: Automatic
Menu set-up Lock
Energy saving mode
Fan ON
A: Automatic
Programming mode
(Technician setting)
C
or
F
ºC: Celsius scale
ºF: Fahrenheit scale
Features:
Attractive modern look with large LCD and backlight
Icons driven information and 1 line of text information
2 Pipes Analog, ON/OFF or Floating
4 Pipes Analog, ON/OFF with local re-heat function
Auto fan and ON/OFF function enable or disable
Precise achieve temperature control with programmable PI function
Independent cooling & heating no occupancy set point
Lockable Set point / Control mode
Selectable internal or external temperature sensor
Change over by contact or external temperature sensor
Celsius or Fahrenheit scale selectable
Anti-freeze protection
BACnet
®
MS/TP @ 9600, 19200, 38400, or 76800 bps
o Selectable device instance and MAC address via menu
o Automatic Device Instance Assignment
o Automatic Baud Rate Detection
o Copy and broadcast configuration to other TFCB controllers
TFCB24F3XYZ1