Technical data
TFCB24F3XYZ1
Specification & Installation Instructions
11
Step Display Description Values
B8
Select “end” address:
Display shows “Select end address”.
Select the last address you want to copy to. You cannot copy on more
than 64 addresses at once.
Range: begin address + 63
Default value: begin address
B9
Copy config result:
Display shows “Copy config succeed” if everything went ok.
If not, you will be able to scroll the addresses and see the error message
associated with each address.
See the Annex section for the complete list of error messages.
Error message example:
Program Mode Error for
address 7
B10
Communication device instance:
Display scrolls “ADJUST DEVICE INSTANC 0153000”.
To change the device, select “YES” and go to next step. If the device
instance is not changed in programming mode (step #53 & 54 or B10 &
B11), it will be automatically modified according to the MAC address.
If you do not want to change the device, go directly to step #B12.
Default value: NO
B11
Communication device instance (cont’d):
Display scrolls the device address value.
You can modify the device address by increasing or decreasing the
blinking digit with “” or “”buttons. To modify the next digit, on right,
press
, to return to the previous digit press .
Range: 0 to 4194302
Increment: 1 digit
Default value: 0153000
B12
C
Internal temperature sensor calibration:
Display scrolls “INSIDE TEMPER SENSOR OFFSET” and temperature read by
internal temperature sensor.
You can adjust the calibration of the sensor by comparison with a known
thermometer. For example if thermostat is installed in an area where
temperature is slightly different than the typical room temperature
(thermostat placed right under the air diffuser).
Range: 10 to 40ºC [50 to 104ºF]
(max. offset ± 5 ºC)
Increment: 0.1ºC [0.2ºF]
B13
C
External temperature sensor calibration:
(If ‘’T 10.0’’ was selected at
step #38)
Display scrolls “EXTERN TEMPER SENSOR OFFSET” and the temperature read by
the external temperature sensor (if connected on the selected input).
If the sensor is not connected or short circuited, the display shows
“Eror”. You can adjust the calibration of the external sensor by
comparison with a known thermometer.
Range: 10 to 40ºC [50 to 104.0ºF]
(max. offset ± 5 ºC)
Increment: 0.1ºC [0.2ºF]