Technical data

Room Controller Thermostat
Specification & Installation Instructions
TROB24T4XYZ1-120926-ESL.doc 1
VAV Thermostat with BACnet
®
Communication Port
T
echnical Data
TROB24T4XYZ1
Inputs 3 Analog input universal (0-10 Vdc or thermistor or digital input dry contact)
Outputs
2 Analog outputs 0-10 Vdc or 2-10 Vdc selectable (2mA max.)
4 Triac output (on/off, pulse 0 or 24 Vac, 250 mA max.),
or 2 Floating output
Power supply 22 to 26 Vac 50/60Hz
Power consumption 1 VA
Set point range 10ºC to 40ºC [50ºF to 104ºF]
External sensor range -40ºC to 100ºC [-40ºF to 212ºF]
Control accuracy Temperature: ±0.4ºC [0.8ºF]
Proportional band 0.5ºC to 5ºC [1ºF to 10ºF] adjustable
Electrical connection 0.8 mm
2
[18 AWG] minimum
Operating temperature 0ºC to 50ºC [32ºF to122ºF]
Storage & Transport Temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95 % non condensing
Degree of protection of housing IP 30 (EN 60529)
Weight 160 g. [0.36 lb]
Interface
C
F
%RH
MO TU WE TH FR SA SU
AM
PM
.
.
.
.
Symbols on display
Cooling ON
33,66,100% output
A: Automatic
Menu set-up Lock
Energy saving mode
Heating ON
33,66,100% output
A: Automatic
Programming mode
(Technician setting)
C
or
F
ºC: Celsius scale
ºF: Fahrenheit scale
Communication
Status
Alarm status
Dimensions
A
B
C
D
E
ºF / º C
Dimension Imperial (in) Metric (mm)
A
2.85 73
B 4.85 123
C
1.00 24
D
2.36 60
E
3.27 83
Features:
Attractive modern look with large LCD and backlight
Icons driven information and 1 line of text information
Selectable analog and digital output
Precise achieve temperature control with programmable PI function
Selectable Fahrenheit or Celsius scale
Manual night set back override
Multi level lockable access menu and set point
Selectable internal or external temperature sensor (10 K)
Change over by contact or external temperature sensor
Pressure sensor input / air flow program
Selectable proportional control band and dead band
Anti-freeze protection
BACnet
®
MS/TP @ 9600, 19200, 38400, 76800bps
Automatic baud rate detection
Automatic device instance configuration
Copy and broadcast configuration to other TROB modules
Selectable device instance and MAC address