Technical data

TROB24T4XYZ1
Specification & Installation Instructions
12
Air Flow & BACnet Program Mode (Available when in Operation Mode; DS1-1 OFF position)
Push on both and
ºF / º C
buttons for 5 seconds to access the user air flow program mode. This menu is accessible only If ‘’PrSd’’ or
‘’PrS
A’’ has been selected at step #32, 33 or 34.
Step Display Description Values
F1
Password:
Display shows
“enter passwrd” and 000.
You have 1 minute to enter the password by incrementing or
decrementing the blinking digit with
and buttons.To modify
following digit on right press
, to return to digit on the left press
ºF / º C
.
When the password is entered press on
. If you do a mistake, you
will see
Eror and the thermostat will return in operation mode. You
need to redo this step.
Password: 637 (corresponding to NEP)
When the password is entered and you are in the balancing mode, this symbol is displayed. Press on the button to advance
to the next program function, press on the
ºF / º C
button to return to previous step and press on the or button to change value.
The system will exit the menus and return to normal function if you navigate through the entire menu or if no button is pressed for 5
minutes, changed values will be saved.
Step Display Description Values
B1
Auto bauds rate:
Display scrolls
“auto BAUDS RATE”. You can enable or disable the Auto
bauds rate function.
When enabled, the thermostat automatically configures its baud rate by
detecting the network speed upon connection. When enabled, the value
cannot be changed manually. When disabled, the baud rate must be set
manually (go to step #B3).
Default value:
Enable (YES)
B2
Auto bauds, current baud:
Display scrolls
“auto comport BAUDS RATE. and the detected baud rate.
Go to step #B4.
Range: 9600, 19200, 38400, 76800
B3
Communication bauds rate:
Display scrolls
“ADJUST COMPORT BAUDS RATE and the value of the baud
rate in kbps. Select the desired baud rate: 9.
6, 19.2, 38.4, 76.8.
Range: 9600, 19200, 38400, 76800
Default value: 76.8 kbps
B4
MAC address:
Display scrolls
“ADJUST MSTP mac address” and the value of the MAC
address. Select the desired MSTP/MAC for communication.
Each device must have a unique MAC address on a network.
Range: 0 to 254
Default value: 0
B5
Copy config:
Display shows
“copy config”.
Select “YES” if you want to copy the configuration of this device to others
on the network.
B6
Select “start” address:
Display shows
“Select begin address”.
Select the first address you want to copy to.
For example if you select MAC address 1 here and 54 in the next step,
all the devices from 1 to 54 will receive the configuration of the current
device.
Range: 0-254
Default value: 0