Instruction Manual

Page 9
7-11
Installation & Operation Manual
Modbus Register Map
Series 380 Register Map
Register Name Address Data Type Read/Write
Sensor Temperature 40001 + 40002 IEEE 754 Float Read Only
Remote Sensor 40003 + 40004 IEEE 754 Float Read Only
Flow Rate 40005 + 40006 IEEE 754 Float Read Only
Flow Total 40009 + 40010 IEEE 754 Float Read Only
Energy Rate 40007 + 40008 IEEE 754 Float Read Only
Energy Total 40011 + 40012 IEEE 754 Float Read Only
Energy Calc Mode 40013 + 40014 IEEE 754 Float Read Only
Flow Filter 40015 + 40016 IEEE 754 Float Read Only
Temp Coef 40017 + 40018 IEEE 754 Float Read Only
Specific Heat 40019 + 40020 IEEE 754 Float Read Only
Fluid Density 40021 + 40022 IEEE 754 Float Read Only
RS-485 Network Configuration – BACnet
Figure 5: Comm Parameters - BACnet
Select BACnet to access the BACnet pull down menus.
Select the Bit Rate (BAUD rate) to match other devices on the network.
BACnet Device Name can be set to help identify this device and location.
BACnet Device ID (Incidence #) is a unique number that identifies this device on the network. Typically, the first part of the
number is the same as the network #, and the last two characters are the same as the address.
Note: The numbering sequence is not a requirement, but can help in system planning.