User Manual

Removing the Low Flow Side
Follow same removal steps for the cover as listed in “Removing the High Flow Turbo Meter Head Assembly” on page 12.
Low Flo
w
Register
High Flow
Register
Cover Seal
Bypass Seal
Turbo Head
Assembly
Bottom Plate
Chamber
Assembly
Figure 13: Removing the low flow side
Servicing the Chamber and Disc
1. Remove the screws holding the bottom plate on the cover assembly.
2. Remove the bottom plate.
3. Remove the chamber retaining strap.
4. Lift out the chamber and disc assembly.
5. Inspect the chamber and parts (see Figure 9) for visible signs of wear. The thrust roller and dovetail insert should be
replaced if worn. Replace the chamber if wear is evident on disc spindle where it contacts the crossbar magnet drive or
the balls or if the disc plate is worn by foreign material. If water deposits are found, remove any mineral deposits from
the disc and chamber interior surfaces. Before replacing the chamber in the meter head, make certain that the area
surrounding the magnet in the meter head is clean.
Recordall® Compound Series Meter, Sizes 2", 3", 4" and 6"
Page 18 September 2013