Instruction Manual
Electronic Preset Meter Model EPM-3, RF 2.4 GHz
METER INSTALLATION
Relieve System Pressure
1. Turn o the power supply to the pump or close the shuto valve.
2. Dispense any uid in the system into a waste container by opening the meter(s).
3. Open all bleed-type master air valves and uid meter(s) in the system.
4. Leave the meter(s) open until ready to pressurize the system.
Pressurized Equipment
This equipment stays pressurized until the pressure is manually relieved. To reduce the risk of injury from fluid spray from the
meter follow the Pressure Relief Procedures when you:
• Are instructed to relieve pressure
• Stop dispensing
• Check, clean, or service any system equipment
• Clean or install nozzles
Grounding
Grounding reduces the risk of static sparking. Ground all system components according to local, state, and federal codes.
Consult the pump user's manual and other system components to ground the following:
• Pump: follow manufacturer's recommendations
• Air and Fluid Hoses: use only grounded hoses
• Air Compressor: follow manufacturers recommendations
• Fluid Supply Container: follow the local code
Possible Explosion and Fire
Movement of fluids through the dispensing system creates static electricity. Static electricity can cause volatile fumes
resulting in an explosion and fire. The dispensing system must be grounded.
Flushing Procedure
NOT:N If the system has multiple dispense positions, begin at the position farthest from the pump and move towards the
pump.
If this installation is new or if the fluid in the lines is contaminated, flush the system before installing the meter(s).
1. Close uid dispense valves at every position.
2. Once the main uid outlet valve at the pump is closed, the air pressure to the pump motor is properly adjusted and
the air valve is opened.
3. Slowly open the main uid valve.
4. Place the hose end in a waste container. Make sure hose is secure so no uid leaks during ushing.
5. Slowly open the dispense valve and allow enough oil to pass through it to ensure that the system is clean.
6. Close the valve and repeat for all dispense positions.
Page 8 November 2012