8. Push on the clapper plate to release the clapper retainer clip, remove and slowly release tension on the clapper. Unbolt
the knuckle joint assembly from outside the body.
9. Bolt the replacement knuckle joint assembly to the body as in step 7.
10. Push on the clapper plate to extend the springs and install the clapper retainer tool, making sure the springs are seated
on the pins. Unbolt the knuckle joint assembly from the bolt hole.
11. Insert the two new 3/8" mounting bolts and washers through the mounting holes in the body. Position the knuckle
joint in place inside the body and nger-tighten both bolts.
12. Torque the knuckle joint mounting bolts to 60 inch-pounds. Remove the clapper retainer tool.
13. Replace the lid and the new gasket.
14. Start system as described in “Performance Checks and System Startup” on page 7.
Yearly inspection is advised for meters installed in water with high levels of debris or contaminates. The measuring chamber
should be cleaned and inspected.
Calibration Check and Adjustment
For calibration check and adjustment of the Turbo Series meters, see the Recordall Turbo Series User Manual.
Recordall® Combo Meter, 8"
Page 10 October 2013