Owner's manual

Menu 4: Characteristic of Setpoint
SRD Main Menu
2 Autostart
3 Valve Action
4 Valve Char.
4 Valve Char.
4.1 Linear
4.2 Eq Perc 1:50
4.3 Quick open
4 Valve Char.
4.1 Linear
4.2 Eq Perc 1:50
4.3 Quick open
M1 234
½ ---½MandLED4flash
A relationship between the inputsignal and valve positionisset.
-1--- LED1lights up
4.1 “Linear”.See Fig. 4.1
--1--LED 2lights up
4.2 “Equal percentage”: Results in an equal percentage characteristic line
withaposition ratioof1:50for a valve of linear characteristic.
See Fig. 4.2
---1- LED3lights up
4.3“Inverse equal perc.”: Resultsinaninversely equal percentage charac-
teristic line with a position ratio of 50:1 foravalveoflinear characteristic.
See Fig. 4.3
3.4.giF2.4.giF1.4.giF
----1LED 4lightsup
“User definedcharacteristic”:
Acharacteristicline entered via
communication (not via local keys) with
2to22supportingpoints)is activated.
A linear characteristic is factoryset.
4 Valve Char.
4.2 Eq Perc 1:50
4.3 Quick open
4.4 Customer
Page 40
Startup
August 2014POS-UM-00009-EN-02