Owner's manual

9.6 Resetting of Configurationand Calibrationto“ex factory” settings
Forthe exchange of the electronicsthe devicemustbeconfigured
whether the pneumatic output is single-actingor double-actingsothat the
controller showsthe correct behavior duringthe next start-up.
Caution: Thecurrent calibrationfor inputs and outputs ,the angle calib-
ration and allother calibrationsare reset to theirfactory definedcondition!
9.6 ResettingofConfiguration andCalibration to “exfactory”settings
–for single-acting pneumatic output
----1 LED4lightsup
Thefactory calibration for single-acting pneumatic output is restored when
pressing (
)key.
9.7 ResettingofConfiguration andCalibration to “exfactory”settings
–for double-acting output
-1--1 LED 1and LED4lightsup
Thefactory calibration for double-acting pneumatic output is restored when
pressing (
)key.
9.8GoOnline withoutAutostart
In principle, thefirst startupruns an Autostart in which theSRD is optimally
adaptedtothe actuator,thenthe SRD goes online and begins to regulate.
This service function sets theSRD directly online, withoutan Autostart.
Only fortest purposes. Not recommendedfor regularuse.
9.9Selection of menulanguage
1)
Oneofthree of theprogrammed languages can be selected (only with
version withLCD display).
Ex-factory the active languageisalways English. Changingto one of the
other twolanguages, can alsotake place during operation.
Thethird menu language can be selected and was alreadyprogrammedin
thefactory accordingtocustomer order.Ifadifferent thirdmenu language
is desired, then the language file can be downloaded from our website:
http://www.foxboro-eckardt.com/download/PLFselector.htm
Thereafter download thefile from thePC via FDT/DTM-Software ontothe
SRD.See also references on theinternet page.
9.10 LCDOrientation
1)
Display normalorturnedby 180°.
9.11 Calibration of Option "Position Feedback 4-20 mA")
Connect24VDC to theterminals of this option andinserta
precise ampmeterintothis loop.
Selecting "Cal. 4 mA" shouldresult acurrent of 4 mA.
Calibrate withkeys (+) or (–).Confirm withkey (
).
Selecting"Cal. 20 mA"should result acurrent of 20 mA.
Calibrate withkeys (+) or (–).Confirmwith key (
).
1) The menus 9.9and 9.10 appearautomaticallyat initial start-up,i.e.ifthe SRDisconnected
thefirst time to theelectricalsupply.
9 Workbench
9.6 Reset all 1
9.7 Reset all 2
9.8 Go Online
9 Workbench
9.6 Reset all 1
9.7 Reset all 2
9.8 Go Online
9 Workbench
9.6 Reset all 1
9.7 Reset all 2
9.8 Go Online
9 Workbench
9.7 Reset all 2
9.8 Go Online
9.9 Menu Lang
9.9 Menu Lang
9.9.1 English
9.9.2 Deutsch
9.9.3 (Francais)
9 Workbench
9.8 Go Online
9.9 Menu Lang
9.10 LCD Orient
9.10 LCD Orient
9.10.1 Normal
9.10.2 Flipped
9 Workbench
9.9 Menu Lang
9.10 LCD Orient
9.11 Cal feedbk
9.11 Cal feedbk
9.11.1 Cal 4mA
9.11.2 Cal 20mA
9.10LCD Orient
9.10.1 Normal
9.10.2 Flipped
C
onfiguration functions forall SRD versions with LCD
Page 51
Startup
August 2014 POS-UM-00009-EN-02