Series 15P Inverter Control Installation and Operating Manual 8/02 MN715P
Table of Contents Section 1 Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 2 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CE Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 1 Quick Start Overview The 1. 2. 3. 4. 5. quick start procedure is as follows: Read the Safety Notice and Precautions in section 2 of this manual. Mount the control. Refer to Section 3, “Physical Installation” procedure. Connect AC power. Refer to Section 3 “Control Installation”. Connect the motor. Refer to Section 3, “Control Installation”. Set the switches and adjust the potentiometers for desired operation. See Figure 1-1.
Figure 1-1 Factory Settings Potentiometers P1 to P6 (arrows indicate factory settings). Accel Decel 10 0.1 Minimum Maximum Current Frequency Frequency Limit 10 60 60 0.1 Coast 0 1/ 2 Base 1/ 2 Lim Lim 50% 100% Torque Boost 0 15% 4Ć20mA Current Remote Speed Remote Command Local Speed Local Command 3 Wire 0Ć10V Voltage Auto REV Disabled 2X Base 50 Hz Switch S1, shown with all switches in OFF position (factory settings).
Section 2 General Information CE Compliance A custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is the responsibility of the system integrator. A control, motor and all system components must have proper shielding, grounding and filtering as described in MN1383. Please refer to this manual for installation techniques for CE compliance.
WARNING: Do not use motor overload relays with an automatic reset feature. These are dangerous since the process may injure someone if a sudden or unexpected automatic restart occurs. If manual reset relays are not available, disable the automatic restart feature using external control wiring. WARNING: This unit has an automatic power up start feature that will start the motor whenever input power is applied and a RUN (FWD or REV) command is issued and maintained.
Section 3 Receiving and Installation Receiving & Inspection The Series 15P Inverter control is thoroughly tested at the factory and carefully packaged for shipment. When you receive your control, there are several things you should do immediately. 1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control. 2. Verify that the control you received is the same as listed on your purchase order. 3.
Control Installation The control must be securely fastened to the mounting surface. Use the four (4) mounting holes to fasten the control to the mounting surface or enclosure. Shock Mounting If the control will be subjected to levels of shock greater than 1G or vibration greater than 0.5G at 10 to 60Hz, the control should be shock mounted. Excessive vibration within the control can cause internal connections to loosen and could lead to component failure or electrical shock hazard.
Cover Removal The cover is made of plastic and could be damaged during removal if handled roughly. Refer to Figure 3-1. Insert a screw driver or small blade tool and pry the cover outward as shown to release the side. When both sides are released, remove the cover. Figure 3-1 Cover Removal Use small screw driver or suitable tool to pry cover slightly outward to release cover from its catch. Use small screw driver or suitable tool to pry cover slightly outward to release cover from its catch.
AC Line Connections A power disconnect should be installed between the input power service and the control for a fail-safe method to disconnect power. The control will remain in a powered-up condition until all input power is removed from the control and the internal bus voltage is discharged. Protective Devices Recommended fuse sizes are based on the following: 115% of maximum continuous current for time delay. 150% of maximum continuous current for Fast or Very Fast action.
Three Phase Wire Size and Protection Devices Table 3-3 Wire Size and Protection Devices - 3 phase Control Rating Input Output Volts HP 230 230 230 230 230 460 460 460 460 460 Input Fuse Wire Gauge Fast Acting Amps Time Delay Amps AWG mm2 6 8 12 15 25 3 4 5 8 12 5 7 9 12 20 2.5 3.5 4.5 6.3 10 14 14 14 14 12 14 14 14 14 14 2.08 2.08 2.08 2.08 3.31 2.08 2.08 2.08 2.08 2.08 1 1.5 2 3 5 1 1.5 2 3 5 Note: All wire sizes are based on 75°C copper wire, 1% line impedance.
115VAC 1 Phase Wire Size and Protection Devices Table 3-4 Wire Size and Protection Devices - 1 phase Control Output Rating HP 0.33 0.5 0.75 1.0 Input Fuse Wire Gauge Fast Acting Amps Time Delay Amps AWG mm2 10 10 15 20 10 10 10 15 14 14 14 14 2.08 2.08 2.08 2.08 Note: All wire sizes are based on 75°C copper wire, 1% line impedance. Figure 3-4 Single Phase AC Power and Motor Connections L1 N Earth Shield wires inside a metal conduit.
230VAC Single Phase Derating for Three Phase Controls Single phase AC input power can be used to power a three phase control. However, the continuous and peak current ratings of the control must be reduced by 35% (derated). Control Output Rating HP 0.75 1 1.5 2 3 Input Fuse Wire Gauge Fast Acting Amps Time Delay Amps AWG mm2 10 12 15 20 25 9 10 15 17.5 25 14 14 14 14 12 2.08 2.08 2.08 2.08 3.31 Note: All wire sizes are based on 75°C copper wire, 1% line impedance.
Motor Brake Connections For motors with spring set brakes, connect the brake power leads and the motor power leads separately. Because the inverter has variable voltage output to the motor, the inverter may not supply enough power at low frequencies for proper brake operation. If using a motor with an internally connected brake, the brake power leads must be connected to a separate power source for proper brake operation. Refer to Figure 3-2 for terminal locations.
Analog Input (S1-7 = OFF) If S1-7 is OFF, the front panel % Speed potentiometer is selected. The J4 inputs are ignored. (S1-7 = ON) One analog input is available at J4-2 and J4-1 as shown in Figure 3-7. The input may be connected to a potentiometer as shown or an input signal can be applied to pin J4-2. The analog signal can be 0-10VDC or 4-20 mA as selected by S1–6 (see Table 3-5). Note: A potentiometer value of 5k to 10k , 0.5 watt may be used.
Digital Inputs (S1-8 = OFF) If S1-8 is OFF, the front panel commands FWD, REV and STOP are selected. The J4 inputs are ignored. (S1-8 = ON) Three inputs are available on the J4 connector. Switch S1-5 determines whether two wire or three wire operation is used. If two wire is selected (S1-5= OFF) the STOP input at J4-6 is not used. Note: Pressing the STOP switch on the front panel keypad will override the J4 commands and cause the motor to decel to a stop.
Section 4 Setup and Operation Overview The operator interface panel is shown in Figure 4-1. Figure 4-1 Operator Interface POWER 60 30 REV 70 20 STOP P1 50 40 FWD Potentiometers P1 Ć P6 S1 DIP Switch (All OFF = factory settings) FAULT P2 80 10 90 0 100 % Speed P3 P4 P5 P6 1 J4 Control Terminal Strip J5 Power Terminal Strip L1 L2 L3 R2 R1 Power GND B- T1 T2 T3 Motor GND POWER LED is on when AC input power is applied to the control.
MN715P Remote Command Remote Speed Local Command 4Ć20mA Current Local Speed 3 Wire 2 Wire 0Ć10V Voltage Auto Manual REV Disabled 2X Base REV Enabled 50 Hz 1X Base S1 60 Hz S1 Settings (OFF = Open; ON = Closed) Setup and Operation 4-2
S1 Settings Continued Switch 1 2 3 4 5 6 7 8 Setting OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Description Base Frequency = 60Hz Base Frequency = 50Hz Maximum frequency limit = Base Frequency (60/50Hz) Maximum frequency limit = 2 X Base Frequency (130 or 110 Hz) Reverse motor rotation ENABLED Does not allow reverse motor rotation Power up Start DISABLED (see notes) Power up Start ENABLED the control will resume operation as soon as power is applied.
Potentiometers P1 - P6 (270° of rotation) Refer to Figure 4-1 for location of potentiometers. ACCEL time – P1 The time required to reach the Maximum Frequency setting of P4. Accelerates at a linear rate. First half (0 to 135° )= 0.1 sec to 10 sec last half (135 - 270°) =10sec to 60 sec 10 Sec. 0.1 Sec. DECEL time – P2 The time required to ramp to a stop. Decelerates at a linear rate. First half (0 to 135° )= 0.
Operation Examples Operating the Control from the Front Panel To place the control in local speed and command mode, place S1-7 and S1-8 in the OFF position. Refer to Figure 4-1 for switch location. Table 4-1 Active Switches for Local Operation Pos. Position and Description OFF Local Speed Reference (front panel potentiometer) OFF Local command input (front panel FWD, REV, STOP) The control can operate as follows: 1. Set the P1 through P6 potentiometers as desired. 2.
Figure 4-3 Remote 0-10VDC 3 Wire Operation J4 0-10VDC signal input S1 5 6 7 8 Pos. ON OFF ON ON Description 3 Wire Voltage mode Remote Speed Ref. Remote commands 1 2 3 4 5 6 GND Speed Command Not used Forward Reverse Stop Figure 4-4 Remote 4-20mA 2 Wire Operation J4 4-20mA signal input S1 5 6 7 8 Pos. OFF ON ON ON MN715P Description 2 Wire Current mode Remote Speed Ref.
Section 5 Troubleshooting The Baldor Series 15P Control requires very little maintenance, if any, and should provide years of trouble free operation when installed and applied correctly. Occasional visual inspection to ensure tight wiring connections and cleaning to remove dust, dirt, or foreign debris which can reduce heat dissipation should be considered. Operational failures called faults are displayed on the LED’s as they occur.
Fault Code 1 – Non Resettable hardware fault (Power LED is blinking). May indicate a HW Surge Current, HW Protect or a Power Module fault is detected. Power LED Blinking Fault LED 1 Blink Action a. Check wiring to ensure a ground fault is not present. b. Make sure the load is not excessive. Fault Code 2 – 2 or 60 second Overload or a % Overload Timer fault. 2 or 60 Second Overload May indicate an overcurrent condition but the control has not tripped, the FWD or REV LED is blinking.
Fault Code 3 – Bus faults. May indicate an Over-voltage, Under-voltage or Precharge fault was detected. Power LED ON Fault LED 3 blinks Action Press Stop to reset the control. If error remains, try these steps to correct the fault. a. Lengthen DECEL time (P2). b. Add external dynamic braking assemblies. c. Correct problem with motor load. d. Check dynamic brake hardware wiring. e. Verify proper AC line voltage. May need step down transformer or line reactor. f.
Section 6 Specifications and Product Data Specifications: Horsepower Input Frequency Output Voltage Output Current Output Frequency Service Factor Duty Overload Capacity Frequency Setting Frequency Setting Potentiometer Rated Storage Temperature: 0.33-1HP @ 115VAC 1-5 HP @ 230VAC 1-5 HP @ 460VAC 50/60Hz ± 5% 0 to Maximum Input Voltage (RMS) See Ratings Table 0 to 130Hz 1.
Display: Control Specifications: Control Method PWM Frequency V/Hz Ratio Transistor Type Torque Boost Brake Torque Accel/Decel Time Base Frequency Frequency Setting Accel/Decel Auto Start Protective Functions Sine wave Carrier input, PWM output Rated @ 7.5kHz Linear with adjustable Torque Boost IGBT (Insulated Gate Bipolar Transistor) 0 to 15% adjustable Up to 60%, external resistor required Separate rates, 0.1 to 60 sec. 50 or 60Hz 0-10VDC, 4-20mA, and Rotary on front panel Separate Accel/Decel rates (0.
Ratings Series 15P Stock Products Catalog No. ID15P1F33-ER ID15P1F50-ER ID15P1F75-ER ID15P101-ER ID15P201-ER ID15P201F5-ER ID15P202-ER ID15P203-ER ID15P205-ER ID15P401-ER ID15P401F5-ER ID15P402-ER ID15P403-ER ID15P405-ER Output Current Rated Input Volts Rated Output Volts HP kW Continuous 60 Sec. Overload 2 Sec. Overload 115 115 115 115 230 230 230 230 230 460 460 460 460 460 230 230 230 230 230 230 230 230 230 460 460 460 460 460 0.33 0.5 0.75 1.0 1 1.5 2 3 5 1 1.5 2 3 5 0.25 0.37 0.56 0.75 0.
Mounting Dimensions 4.396 (112) POWER FWD FAULT 40 50 70 10 90 0 100 % Speed REV 20 7.210 (183) 7.654 (195) STOP 60 30 80 For mounting, use four #8 x 1–3/8” long screws. A = 5.660 (144) for 230VAC, 5hp A = 4.945 (126) all other sizes A OM000A03 6-4 Specifications and Product Data 4.
BALDOR ELECTRIC COMPANY P.O.